Table 3-1: Current Requirements.

 

 

 

 

 

 

Module/Device

Standby mA

 

Alarm mA

2500 with LCD display

170

 

310*

2500 without LCD display

105

 

250

CAM (Class A module)

0

 

25

RALCD (Remote Annunciator)

95

 

115

ZDACT (Digital Alarm Communicator)

30

 

50

MBM module

30

 

15 (250 momentary)

PAM-1 or PAM-2 Relay

15

 

15

*Includes one zone short circuit current.

 

 

 

Table 3-2: Secondary Power Requirements.

NFPA-72 National Fire Alarm Code

 

Standby Time

 

Alarm Time

Local Systems

 

 

 

24 hrs.

 

 

5 min.

Auxiliary Systems

 

 

 

60 hrs.

 

 

5 min.

Remote Station Systems

 

 

60 hrs.

 

 

5 min.

Central Station Systems

 

 

24 hrs.

 

 

5 min.

 

 

 

 

 

 

 

 

 

 

 

Table 3-3: Calculation Table.

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

3

 

4

5

 

6

Module/Device

 

Qty.

Standby mA Per Unit

Total Standby

Alarm mA Per Unit

Total Alarm

 

 

 

 

 

Current

 

 

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total mA

 

Total mA

 

Convert to A

X 0.001

Convert to A

X 0.001

Total A

 

Total A

 

Multiply by hours

X

AH for 5 mins.

÷ 12

from table 2

 

 

 

Total Standby AH

 

Total Alarm AH

 

 

 

 

+ Total Standby AH

 

 

 

 

Total AH

 

 

 

 

Efficiency Factor

÷ 0.85

 

 

 

Required AH

 

Select a battery such that the battery’s amp hour rating meets or exceeds the calculated amp hour requirement (44AH maximum).