CPG #2561255 |
| FIRELARM 2500 Operating Manual | |
Table |
|
| |
|
|
|
|
Module/Device | Standby mA |
| Alarm mA |
2500 with LCD display | 170 |
| 310* |
2500 without LCD display | 105 |
| 250 |
CAM (Class A module) | 0 |
| 25 |
RALCD (Remote Annunciator) | 95 |
| 115 |
ZDACT (Digital Alarm Communicator) | 30 |
| 50 |
MBM module | 30 |
| 15 (250 momentary) |
15 |
| 15 | |
*Includes one zone short circuit current. |
|
|
|
Table 3-2: Secondary Power Requirements.
| Standby Time |
| Alarm Time | |||||
Local Systems |
|
|
| 24 hrs. |
|
| 5 min. | |
Auxiliary Systems |
|
|
| 60 hrs. |
|
| 5 min. | |
Remote Station Systems |
|
| 60 hrs. |
|
| 5 min. | ||
Central Station Systems |
|
| 24 hrs. |
|
| 5 min. | ||
|
|
|
|
|
|
|
| |
|
|
| Table |
|
|
| ||
|
|
|
|
|
|
|
|
|
1 |
| 2 | 3 |
| 4 | 5 |
| 6 |
Module/Device |
| Qty. | Standby mA Per Unit | Total Standby | Alarm mA Per Unit | Total Alarm | ||
|
|
|
|
| Current |
|
| Current |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Total mA |
| Total mA |
| |
Convert to A | X 0.001 | Convert to A | X 0.001 | |
Total A |
| Total A |
| |
Multiply by hours | X | AH for 5 mins. | ÷ 12 | |
from table 2 |
|
|
| |
Total Standby AH |
| Total Alarm AH |
| |
|
|
| + Total Standby AH |
|
|
|
| Total AH |
|
|
|
| Efficiency Factor | ÷ 0.85 |
|
|
| Required AH |
|
Select a battery such that the battery’s amp hour rating meets or exceeds the calculated amp hour requirement (44AH maximum).