A.3 Style Z (Class A) Module for NAC circuits (CAM)
UL LISTED: For use with the FireLarm 2500 Part No.
TRANSIENT PROTECTED
BUILT IN 5.1K END OF LINE RESISTOR
POWER REQUIREMENTS IN ALARM: Approx. 25mA @ 24VDC from control panel notification appliance circuit
The Model CAM Style Z (Class A) Module is designed to be used with the FireLarm 2500 Fire Control Panels to convert a single Style Y (Class B) notification appliance circuit to a Style Z (Class A) circuit (one module is required for each notification appliance circuit). The module is provided with snap track which is mounted to the cabinet via
Figure A-3. CAM Module Wiring.
CAM |
|
| - | TO INDICATING |
|
|
| RED | APPLIANCE CIRCUIT |
|
|
| TERMINALS. | |
|
|
|
| REMOVE EOL RESISTOR. |
|
|
| + | POLARITY SHOWN IS FOR |
|
|
| BLACK | STANDBY |
|
|
| CONDITION | |
1 | 2 | 3 | 4 |
|
+ | + | - | - |
|
| EXTERNAL |
|
| |
| INDICATING |
|
| |
APPLIANCES |
|
|
FigureA-4. CAMModule Location.
USE FOAM TAPE TO MOUNT SNAP | ||
TRACK IN CABINET AND SECURE |
| |
WITH TWO #6 SHEET METAL |
| |
SCREWS BEFORE MOUNTING CAM | ||
MODULE IN SNAP TRACK | ||