3.8Notification Appliance Circuits Connections
The control panel has two Style Y (Class B) notification appliance circuits which can be upgraded to Style Z (class A) by the addition of a model CAM (Class A Module). One module is required for each circuit that is to be upgraded. See Appendix A for more information.
Thenotificationappliancecircuitsare power limited, regulated 24 VDC rated at 2.0 amperes max each. (Total system currentnot to exceed 2.5 A.)
| Figure |
Diagram |
Notes for Figure 3-7:
1.Power inputs (not power limited). Wire wrap to standoff for strain relief.
2.Battery leads (not power limited).
3.Use left hand knockouts for
4.Use right hand knockouts for power limited wiring.
5.Connect earth ground to corner of main board using a #6 ring terminal or wire and ring provided.