3.8Notification Appliance Circuits Connections

The control panel has two Style Y (Class B) notification appliance circuits which can be upgraded to Style Z (class A) by the addition of a model CAM (Class A Module). One module is required for each circuit that is to be upgraded. See Appendix A for more information.

The￿￿￿￿￿￿￿￿￿notification￿￿￿￿￿￿￿appliance￿￿￿￿circuits￿￿￿￿￿are ￿￿￿￿￿￿￿power limited,￿￿￿￿ regulated 24 VDC rated at 2.0 amperes max each. (Total system current￿not to exceed 2.5 A.)

￿￿￿￿￿￿￿￿ ￿ ￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿

 

Figure 3-7. Wire Routing

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Diagram

￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Notes for Figure 3-7:

1.Power inputs (not power limited). Wire wrap to standoff for strain relief.

2.Battery leads (not power limited).

3.Use left hand knockouts for non-power limited wiring.

4.Use right hand knockouts for power limited wiring.

5.Connect earth ground to corner of main board using a #6 ring terminal or wire and ring provided.

6.All wiring must be wire-wrapped to a standoff or other mechanically secure location.

All field-installed wiring connected to this panel must maintain a spacing of ¼ inch between all power-limited conductors and all electrical light, power, Class 1, or non-power limited conductors.

3

4

5

A

B

C

D

E

3-7

Page 21