[ Section 3-Operation ]

[ Page 16]

If a blast cycle is cancelled and the defrost thermostat is measuring 1°C/32°F or less, the BLAST CHILLER automatically goes into a defrost cycle.

When the BLAST CHILLER is in the defrost mode the “Cabinet Temp” window of the control panel will display “DEF” During the defrost cycle some fans will stop running. This is normal. When the defrost cycle is finished the compressor will run for approximately 90 seconds before the fans operate.

Following every defrost period there is a 3 minute period during which a blast cycle cannot be selected. This short interval is to allow for the water created by the defrost mode to dissipate. The cabinet is now ready to start another blast cycle if desired.

During the defrost operation it is safe to leave products inside the blast chiller.