[ Section 5- Troubleshooting ]

[ Page 19a ]

ALARM CODES

7-Segment Display

The left hand window shows the cabinet wall temperature.

The right hand displays show the probe temperatures during a blast cycle, and are normally blank during store. If a probe fails it will indicate pf (probe failure) during a blast.

Cab temp window also acts as a count up timer in probe blast.

If there is an alarm condition, the top probe display will show an alarm number a0 to a7 during store (see table below), but will still show the probe temperature during blast.

7-Seg Display

 

Alarm Condition

 

 

a0

AIR ON SENSOR FAILURE

 

 

a1

WALL SENSOR FAILURE

 

 

a2

FIN SENSOR FAILURE

 

 

a3

FOOD PROBE 1 FAILURE *

 

 

a4

FOOD PROBE 2 FAILURE

 

 

a5

FOOD PROBE 3 FAILURE

 

 

a6

SPARE

 

 

a7

POWER CUT DETECTED

 

 

 

* (Top Display On Front Panel Used For 3 Probe Systems)

Note: for each probe only one audible alarm and alarm printout is allowed to be issued each day. This is to prevent excessive paper use and noise nuisance in the event of an intermittent probe failure. However, repeated probe failures are displayed on the probe display window, (top window in the case of 3 probe panels)

Page 22
Image 22
Cres Cor CCBC-12-75, CCBC-4-35, CCBC12-UA-100 service manual Alarm Codes, Segment Display