The Dell Storage Center Dell Storage Client Administrator’s Guide describes how to use the Dell
Storage Client to manage a Storage Center.
Installation and Configuration
Before you begin installation, make sure that the site where you plan to install the storage system has 208
V power from an independent source or a rack power distribution unit with a UPS. (110 V power is not
supported.)
In addition, verify that there is a 5U space in the lower 20U of the rack to install the storage system. If you
plan to install the storage system above the lower 20U of a rack, a customer-provided mechanical lift
must be used to avoid injury.

Safety Precautions

Always follow these safety precautions to avoid injury and damage to Storage Center equipment.
If equipment described in the document is used in a manner not specified by Dell, the protection
provided by the equipment may be impaired. For your safety and protection, observe the rules described
in the following sections.
NOTE: See the safety and regulatory information that shipped with each Storage Center
component. Warranty information may be included within this document or as a separate
document.

Installation Safety Precautions

Follow these safety precautions:
Dell recommends that only individuals with rack-mounting experience install an SCv2080 storage
system in a rack.
You need at least two people to lift the storage system chassis from the shipping box and three
people to install it in the rack. The empty chassis weighs approximately 62kg (137 lbs).
Make sure the storage system is fully grounded at all times to prevent damage from electrostatic
discharge.
When handling the storage system hardware, you should use an electrostatic wrist guard (not
included) or a similar form of protection.
The storage system chassis MUST be mounted in a rack; the following safety requirements must be
considered when doing so:
The rack construction must be capable of supporting the total weight of the installed chassis and the
design should incorporate stabilizing features suitable to prevent the rack tipping or being pushed
over during installation or in normal use.
When loading a rack with chassis, fill from the bottom up; empty from the top down.
To avoid danger of the rack toppling over, do not slide more than one chassis out of the rack at a
time.
The storage system must be operated with low-pressure rear exhaust installation [back pressure
created by rack doors and obstacles not to exceed 5 Pascals (0.5 mm water gauge)].
The rack design should take into consideration the maximum operating ambient temperature for the
unit, which is 35°C.

Unpacking Storage Center Equipment

Unpack the storage system and identify the items in your shipment.