3.Fill the outer tank to correct system pressure. Correct pressure will vary with each application.
NOTICE
Typical residential system fill pressure is 12 psi. System pressure will increase when system temperature increases. Operating pressure of the system should never exceed 25 psi.
4.Allow air to escape from the outer tank by opening the automatic air vent provided with the ELITE.
5.Purge air in each zone of the primary sys- tem through the purge valve. Open air vents to allow air to be purged in the zones.
6.Once the system is completely filled and purged of all air, check the system pressure and check for leaks.
Check Low Water Cut-Off Device
-The ELITE is provided with a factory installed Low Water
-Remove the front jacket panel and check for continuity across the low water
Check For Gas Leaks (if applicable)
WARNING
Prior to
WARNING
Propane installations only - The propane supplier mixes an odorant with the propane to make its presence detectable. In some cases the odorant can fade and the gas may no longer have an odor.
Prior to
Check Thermostat Circuit
-Unplug the Room Thermostat
-Connect a voltmeter across the end ter- minals of the male half of the Room Thermostat
-Close each thermostat, zone valve and relay in the external circuit one zone at a time and check the voltage reading across the plug.
-There should NEVER be voltage mea- sured at the plug.
-If voltage is measured at the plug under any condition, check and correct the external wiring.
NOTICE
In systems using
39