Delta Electronics VFD007S23A manual Gnd

Models: VFD007S23A

1 186
Download 186 pages 25.41 Kb
Page 38
Image 38

 

 

Chapter 2 Installation and WiringVFD-S Series

Terminal

Terminal Function

Factory Settings (NPN mode)

 

Symbol

ON: Connect to GND

 

 

 

 

 

 

 

 

 

M4

Multi-function input 4

 

 

 

 

 

 

 

 

 

 

M5

Multi-function Input 5

 

 

 

 

 

 

 

 

 

+17V

DC Voltage Source

+17VDC, 20mA used for PNP mode.

 

 

 

 

 

 

GND

Digital Signal Common

Common for digital inputs and used for NPN

 

mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AFM circuit

 

 

 

 

 

 

AFM

 

 

AFM

Analog output meter

 

 

0~10V

 

 

 

ondometer

 

 

 

 

 

Max. 2mA

 

 

 

Internal Circuit

GND

 

 

 

 

 

 

 

RA

Multi-function Relay output

Resistive Load:

 

 

 

(N.O.) a

 

 

 

 

5A(N.O.)/3A(N.C.) 240VAC

 

 

 

 

 

 

 

Multi-function Relay output

5A(N.O.)/3A(N.C.) 24VDC

 

 

 

RB

Inductive Load:

 

 

 

(N.C.) b

1.5A(N.O.)/0.5A(N.C.) 240VAC

 

 

 

 

 

 

 

1.5A(N.O.)/0.5A(N.C.) 24VDC

 

 

RC

Multi-function Relay common

Refer to Pr.3-06 for programming

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum 48VDC, 50mA

 

 

 

 

 

Refer to Pr.3-01 for programming

 

 

 

 

MO1-DCM

Max: 48Vdc

 

 

 

 

50mA

 

 

 

 

 

 

 

Multi-function Output 1

Mo1

 

 

 

MO1

 

 

 

 

(Photocoupler)

 

 

 

 

 

 

 

 

 

 

 

MCM

 

 

 

 

 

internal circuit

 

 

 

 

 

 

 

 

 

MCM

Multi-function output common

Max. 48Vdc 50mA

 

 

 

 

 

 

 

+10V

Potentiometer power supply

+10VDC 10mA (variable resistor: 3~5kohm)

 

 

 

 

 

 

 

Revision August 2006, SE08, SW V2.61

2-25

Page 38
Image 38
Delta Electronics VFD007S23A manual Gnd