Chapter 5 ParametersVFD-S Series

2-01Source of Operation Command

 

 

Factory Setting: d0

Settings

d0

Controlled by the keypad

 

d1

External terminals. Keypad STOP/RESET enabled.

 

d2

External terminals. Keypad STOP/RESET disabled.

 

d3

RS-485 serial communication (RJ-11). Keypad STOP/RESET

 

 

enabled.

 

d4

RS-485 serial communication (RJ-11). Keypad STOP/RESET

 

 

disabled.

When the AC drive is controlled by an external source, please refer to parameter group 4 for

detailed explanations on related parameter settings.

2-02

Stop Method

 

 

 

 

 

 

Factory Setting: d0

 

Settings

d0

STOP: ramp to stop

E.F.: coast to stop

 

 

d1

STOP: coast to stop

E.F.: coast to stop

 

 

The parameter determines how the motor is stopped when the AC motor drive receives a

valid stop command or detects External Fault.

 

Ramp:

the AC motor drive decelerates to Minimum Output Frequency (Pr.1-05)

 

 

according to the deceleration time set in Pr.1-10 or Pr.1-12 and then stops.

Coast:

the AC motor drive stops the output instantly upon command, and the motor

free runs until it comes to a complete standstill.

The motor stop method is usually determined by the characteristics of the motor load and how frequently it is stopped.

(1)It is recommended to use “ramp to stop” for safety of personnel or to prevent material from being wasted in applications where the motor has to stop after the drive is stopped. The deceleration time has to be set accordingly.

(2)If motor free running is allowed or the load inertia is large, it is recommended to select “coast to stop”. For example: blowers, punching machines, centrifuges and pumps.