Desa CDL3924NT, CDL3924PT, LSL3124P installation manual Continued, Minimum Fireplace Clearance To

Models: LSL3124P CDL3924PT CDL3924NT

1 32
Download 32 pages 9.88 Kb
Page 9
Image 9
MINIMUM FIREPLACE CLEARANCE TO

INSTALLATION

Continued

INSTALLATION AND CLEARANCES FOR VENT-FREE OPERATION

Manual background WARNING: Maintain the mini- mum clearances. If you can, pro- videgreaterclearancesfromfloor, ceiling and adjoining wall.

MINIMUM FIREPLACE CLEARANCE TO

COMBUSTIBLE MATERIALS

Side Wall

Ceiling

 

 

 

 

16"

 

42"

 

 

 

 

 

 

LOG SIZING REQUIREMENTS

 

 

 

 

 

 

Minimum Firebox

 

 

 

 

 

 

Height

Depth

Front

 

Rear *

 

 

Width

 

Width

17"

14"

28"

 

21"

 

 

 

 

 

* Measured at 14" depth.

Carefully follow the instructions below. This will ensure safe installation into a masonry, UL127-listed manufactured fireplace or listed vent-free firebox.

MinimumClearances ForSideCombustible Material, Side Wall and Ceiling

A.Clearances from the side of the fireplace cabinet to any combustible material and wall should follow diagram in Figure 4.

Example: The face of a mantel, bookshelf, etc. is made of combustible material and protrudes 3 1/2" from the wall. This combus- tible material must be 4" from the side of the fireplace cabinet (see Figure 4).

Note: When installing your gas logs into a manufactured firebox, follow firebox manufacturerʼs instructions for minimum clearances to combustible materials.

B.Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.

Example

*

*Minimum 16 inches from Side Wall

Figure 4 - Minimum Clearance for

Combustible to Wall

NOTICE: Manual control heaters maybeusedasaventedproduct. If so, you must always run heater with chimney flue damper open. If running heater with damper open, noncombustible material above fireplace opening is not needed. Go to Installing Damper Clamp Accessory for Vented Operation, page 11.

MINIMUM NONCOMBUSTIBLE

MATERIAL CLEARANCES

If Not Using Mantel

Note: If using a mantel proceed to If Using Mantel. If not using a mantel, follow the information on this page.

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory. See Figure 5, page 10, for minimum clearances.

If Using Mantel

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombus- tible material must extend at least 8 inches up). If noncombustible material is less than 12", you must install the fireplace hood accessory. Even if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figures 5, 6 and 7, page 10, for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 11.

111347-01E

www.desatech.com

9

Page 9
Image 9
Desa CDL3924NT, CDL3924PT, LSL3124P installation manual Continued, Minimum Fireplace Clearance To