DVFH34, DVFH34P

DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)

VENTING

INSTALLATION

Continued

Note: Install restrictor into 4" collar of stove as shown.

FD30

30˚ Starter/

Adapter Required

Venting with Two 90° Elbows

Vertical (V1)

Horizontal (H)

5' min.

6' max.

6' min.

12' max.

7' min.

18' max.

8' min.

20' max.

Note: Vertical (V1) + Vertical (V2) = 20' max.

Note: Install restrictor into 4" collar of stove as shown.

FD30

30˚ Starter/

Adapter

Required

Vertical Venting

V = 40' max.

Figure 27 - Vertical Rigid Venting Configuration With No Horizontal Run

Figure 26 - Vertical Rigid Venting Configuration Using Two 90° Elbows

14

106394

Page 14
Image 14
Desa DVFH34P installation manual Vertical Venting, Vertical Rigid Venting Configuration With No Horizontal Run