Desa VSGF28PTE, VSGF28NTE Checking GAS Connections, Pressure Testing Gas Supply Piping System

Models: VSGF28PTE VSGF28NTE

1 32
Download 32 pages 22.96 Kb
Page 15
Image 15

INSTALLATION

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip- ing and connections, internal and external to unit, for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak de- tection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1. Disconnect fireplace with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply pipping. Pres-

sures in excess of 1/2 psig will damage fire-

place gas regulator.

Pressure Testing Fireplace Gas Connections

1.Open equipment shutoff valve (see Figure 21).

2.Open main gas valve located on or near gas meter for natural gas or open propane/LP sup- ply tank valve.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from equipment shutoff valve to gas control valve (see Figure 22 or 23). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light fireplace (see Operating Fireplace, pages 17 and 18). Check all other internal joints for leaks.

7.Turn off fireplace (see To Turn Off Gas to Appliance, page 18).

OpN en

EquipmentPOSIT

Shutoff

Valve

POS

ClosedO

Figure 21 - Equipment Shutoff Valve

2.

Cap off open end of gas pipe where equip-

 

ment shutoff valve was connected.

3.

Pressurize supply piping system by either

 

opening propane/LP supply tank valve for

 

propane/LP gas or opening main gas valve lo-

 

cated on or near gas meter for natural gas, or

 

by using compressed air.

4.

Check all joints of gas supply piping system.

 

Apply noncorrosive leak detection fluid to all

 

joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

Gas Control Valve

Equipment

Shutoff

Valve

Gas Meter

6. Reconnect fireplace and equipment shutoff

valve to gas supply. Check reconnected fit-

tings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 21).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve lo- cated on or near gas meter for natural gas, or using compressed air.

3.Check all joints from gas meter for natural or propane/LP supply to equipment shutoff valve (see Figure 22 or 23). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Figure 22 - Checking Gas Joints (Natural

Gas Only)

Equipment Shutoff Valve

Propane/LP

Supply Tank

Gas Control Valve

Figure 23 - Checking Gas Joints

(Propane/LP Gas Only)

113135-01A

www.desatech.com

15

Page 15
Image 15
Desa VSGF28PTE, VSGF28NTE installation manual Checking GAS Connections, Pressure Testing Gas Supply Piping System