20

FIREPLACE INSTALLATION

Connecting Fireplace To Gas Supply

 

Checking Gas Connections

 

 

FIREPLACE INSTALLATION

Continued

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gently pulling forward.

2.Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas supply to control valve (see Figure 32).

4.Check all gas connections for leaks. See Checking Gas Connections.

 

Red Surface Indicates

Equipment

For Propane/LP Use Only

Flexible Gas Line

Shutoff Valve

Do NOT Kink

1/2" NPT Incoming

 

 

Gas Line

Inlet Pressure Tap

Outlet Pressure Tap

 

Note: Wire Connections Not Shown for Clarity

Figure 32 - Connecting Flexible Gas Line to Electronic Valve

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Reconnect fireplace and equipment shutoff valve to gas sup- ply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 33).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

3.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment

Shutoff Open

Valve

Closed

Figure 33 - Equipment Shutoff Valve

Propane/LP

Equipment

Supply Tank

Shutoff

 

 

Valve

 

Gas Valve

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

4.Check all joints of gas supply piping system. Apply noncorro- sive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment

Shutoff

Valve

Gas

Meter

Gas Valve

Figure 35 - Checking Gas Joints for Natural Gas Fireplace

For..com

108860

Page 20
Image 20
Desa (V)T32EP, (V)T36EP SERIES Connecting Fireplace to GAS Supply, Checking GAS Connections, Installation Items Needed

(V)T32EP, V)T32EN, (V)T36EP SERIES, (V)T36EN SERIES specifications

The Desa (V)T36EP Series, (V)T32EP, (V)T36EN Series, and (V)T32EN represent a significant advancement in heating technology, designed to deliver efficient warmth and comfort in various environments. These models are notable for their innovations, user-friendly features, and durability, making them a popular choice among consumers seeking effective heating solutions.

One of the main features of the Desa (V)T36EP and (V)T32EP models is their energy efficiency. Engineered with advanced combustion systems, these units optimize fuel usage, translating to lower energy bills while maintaining superior heating performance. The energy efficiency ratings of these models are impressive, making them not only environmentally friendly but also cost-effective in the long run.

The (V)T36EN and (V)T32EN series offer similar energy-efficient heating solutions without compromising on output capacity. Both series employ a robust design that ensures consistent performance even in colder climates. The built-in thermostat and multiple heat settings allow users to customize their heating experience, ensuring maximum comfort geared to individual preferences.

Technologically, the Desa models boast a range of innovative features. The automatic shut-off function promotes safety by turning the unit off when it reaches an unsafe temperature or if it tips over. This feature is crucial for families with children and pets, providing peace of mind. Additionally, the user-friendly controls make adjusting settings straightforward, further enhancing the user experience.

Durability is another key characteristic of the Desa (V)T36EP, (V)T32EP, (V)T36EN, and (V)T32EN series. Constructed from high-quality materials, these units are designed to withstand the rigors of daily use. The stylish yet practical design allows them to blend seamlessly with various decors while providing reliable heating.

Furthermore, the models in this series are designed for ease of maintenance. The accessible filters and components make routine cleaning simple, ensuring the units operate efficiently over their lifespan.

In conclusion, the Desa (V)T36EP SERIES, (V)T32EP, (V)T36EN SERIES, and (V)T32EN models represent a perfect blend of efficiency, safety, and durability, catering to modern heating needs. Their advanced features and technologies provide an excellent solution for consumers looking for long-lasting and reliable heating options in any living space.