Fireplace

Installation

Continued

Pressure Testing Fireplace Gas

Connections

1. Open equipment shutoff valve (see Figure 34, page 23).

2. Open propane/LP supply tank valve for propane/LP fireplace or main gas valve located on or near gas meter for natural gas fireplace.

3. Make sure control knob of fireplace is in the OFF position.

4. Check all joints from equipment shutoff valve to gas valve (see Figure 35 or Figure 36, page 23). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5. Light fireplace (see Operating Fireplace, page

27). Check all other internal joints for leaks.

6. Turn off fireplace (see To Turn Off Gas to Ap- pliance, page 28).

Installing optional wall Mount Switch - gwmS2

1.Connect one terminal of 25 ft. wire for the wall switch to the TPTH terminal on the valve. Con- nect remaining wire terminal to the TH terminal on the valve. Make sure that the wire terminals are in the positions on the unit as pictured in Figure 37. If wires are not connected as shown the switch will not work.

2.Route the 25 ft. wire through openings pro- vided on the sides of the burner system to a convenient location to mount your switch.

3.Connect one bare wire end to each of the terminals of GWMS2 wall switch.

4.Install the wall switch and cover in the wall.

To Wall Switch

Accessory

Figure 37 - Connecting Wall Switch to

Control Valve

Installing Optional Wireless hand-held REMOTE CONTROL HRC100 and HRC200 Series

NOTICE: Use only alkaline bat- teries (not included).

Installing Remote Receiver

1. Open bottom louver and locate the switch bracket on the right.

2. Unscrew the switch bracket. Lean bracket forward so you are able to access the back of the remote receiver.

3. Locate the battery clip mounted on the back of the receiver. Slide a 9-volt alkaline battery (not included) through the clip (see Figure 38).

4. Attach the terminal wires to the battery.

5. Connect wires from receiver to TH and TPTH to control valve (see Figure 39).

6. Replace the switch bracket.

Receiver

9-Volt Alkaline Battery

Terminal

Wires

Battery Clip

Figure 38 - Attaching Alkaline Battery to

Receiver

To Optional

Remote

Accessory

Figure 39 - Control Valve Terminals

24

www.desatech.com

116200-01H

Page 24
Image 24
Desa (V)VC36P Series Installing optional wall Mount Switch gwmS2, Pressure Testing Fireplace Gas Connections