INSTALLATION
Flue Opening Specifications Check Gas Type
Venting Specifications for Installation
INSTALLATION
CAUTION: Do not remove the metal data plates attached to the burner pan. The data plates contain important warranty and safety information.
WARNING: Before installing in a solid fuel burn- ing fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney flue may create and distribute soot within the house. Inspect chimney flue for damage.
NOTICE: Installation, service, and repair of this appli- ance must be performed by a qualified installer, ser- vice agency, company or gas supplier experienced with this type of gas appliance. Only factory autho- rized components listed in these instructions may be used in accordance with the manufacturer’s instruc- tions and all codes and requirements of the authority having jurisdiction. Any modifications to this kit, or use of unauthorized components or accessory items will void the manufacturer’s warranty, and may result in a hazardous condition.
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural gas, you must convert the appliance to propane/LP. Follow the instruc- tions on pages 6 and 7.
If the fireplace does not have a gas supply
VENTING SPECIFICATIONS FOR
INSTALLATION
The fireplace chimney flue and vent must be drafting properly. To check the vent for proper drafting: Light a tightly rolled newspa- per on one end and place it at the inside front edge of the fireplace. Observe the smoke and be sure the vent is properly drawing it up the chimney. If the smoke spills out into the room, extinguish the flame and remove any obstruction until proper venting is achieved.
The chimney flue damper must be fixed open to provide a minimum of 81 sq. in. of free air opening during operation of this log set. A multipurpose damper clamp is provided to fix the damper in position.
The minimum flue sizes shown in Figure 2 are based on a 6' chimney height using round pipe. Your minimum flue size will vary based on input rate and chimney height. Refer to the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 6.6, for details.
FLUE OPENING SPECIFICATIONS
Note: This vented appliance must be installed only in a
The charts in Figure 2 indicate technical information regarding the installation of your gas log set. Please make sure that all of the specifications shown are applicable before installation is attempted.
The fireplace must include a working flue and venting system with the minimum openings shown in the Figure 2.
| Btu Input | Btu Input | Burner Orifice |
| |||
DESCRIPTION | Natural | Propane/LP | Natural | Propane/LP | |||
Gas | Gas | In. | Num. | In. |
| Num. | |
18" Single Burner | 50,000 | 40,000 | .116 | 32 | .081 |
| 46 |
24" Single Burner | 60,000 | 50,000 | .120 | 31 | .082 |
| 45 |
18" Dual Burner | 55,000 | 45,000 | .116 | 32 | .082 |
| 45 |
24" Dual Burner | 65,000 | 55,000 | .138 | 29 | .086 |
| 44 |
30" Dual Burner | 70,000 | 60,000 | .1405 | 28 | .089 |
| 43 |
|
|
|
|
|
|
|
|
Figure 2 - Technical Information Charts
MINIMUM FIREBOX SIZES
LOG | FRONT | BACK |
|
| MINIMUM |
SIZE | WIDTH | WIDTH* | DEPTH | HEIGHT | FLUE SIZE |
|
|
|
|
|
|
18" | 34" | 16" | 14" | 18" | 8" diam. |
24" | 35 3/4" | 17" | 15 1/2" | 18" | 8" diam. |
30" | 42" | 27" | 18" | 18" | 9" diam. |
*At depth indicated
SPECIFICATIONS (W.C.)
| FUEL INLET | MANIFOLD | ||
| PRESSURE | PRESSURE | ||
|
|
|
|
|
|
| Min. | Max. |
|
NG |
| 7 | 10.5 | 6 |
LP |
| 11 | 14 | 10 |
For morevisit www..com
901268