Desa WCM-42J Venting Installation, Continued, Flashing Installation, Roof Opening Measurements

Models: WCM-36J WCM-50J WCM-42J

1 40
Download 40 pages 9.16 Kb
Page 11
Image 11
Figure 16 - Flashing Installation

Venting Installation

Continued

5.Add next sections of pipe until end penetrates roof line. Check to see that proper clearances are maintained. Extend chimney by adding sections of double wall pipe until pipe is minimum of 30" above highest point of roof cutout. Termination and chimney must extend a minimum of 36" above highest point where it passes through roof.

Flashing installation (v6f-10dm or v12f-10dm)

Determine the flashing to be used with the roof opening chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nail- ing through shingles (see Figure 16). DO NOT NAIL THROUGH FLASHING CONE.

17" Min.

Figure 15 - Roof Opening Measurements 1" Min.

1" Min.

30" Min.

1" Min.

Opening "A"

Installing Flashing on a Metal Roof When installing the flashing on a metal roof, it is required that putty tape be used between the flashing and the roof. The flashing must be secured to the roof using #8 x 3/4" screws and then sealed with roof coating to prevent leak- age through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.

Storm Collar

Overlap

Shingles Top

Flashing

and Sides Only

Pitch

Slope

Opening

Used Flashing

 

 

"A" Max.

Model No.

Flat

17"

V6F-10DM

0-6/12

26.6°

19"

V6F-10DM

6/12-

45.0°

24"

V12F-10DM

12/12

 

 

 

 

Roof Opening 36" Models

19.5" Min.

 

30" Min.

 

 

 

 

 

2" Min.

 

 

 

 

2" Min.

 

 

2" Min.

 

 

 

 

Opening "A"

Cone

Nail Only

Outer

Perimeter

of Flashing

Underlap Shingles

at Bottom

Figure 16 - Flashing Installation

Storm Collar Installation (SC2-1)

Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see Figure 17). Apply waterproof caulk around the perimeter of the collar to provide a proper seal.

Pitch

Slope

Opening

Used Flashing

 

 

"A" Max.

Model No.

Flat

19.5"

V6F-10DM

0-6/12

26.6°

22'

V6F-10DM

6/12-

45.0°

27"

V12F-10DM

12/12

 

 

 

Roof Opening 42" and 50" Models

Figure 15 - Roof Opening Measurements

Chimney

Waterproof

Pipe

Caulk

Storm

Flashing

Collar

Figure 17 - Storm Collar

122273-01A

www.desatech.com

11

Page 11
Image 11
Desa WCM-42J, WCM-36J Venting Installation, Continued, Flashing Installation, Roof Opening Measurements, Storm Collar