To p S i d e C o n t r o l I n s t r u c t i o n s

Preset Filter Cycles (cont.)

1 minute after the spa is energized. The second filter cycle will begin

12 hours after the start of the first filter cycle. Filter duration is programm- able at the topside panel for 0, 1, 2, 3, 4 or 12 hours. To program, press the SET pad, then the JETS pad. Press the SET pad again and F2 will be displayed on the panel. (F2 is the default filter time and indicates a 2 hour cycle). Continue pressing SET to cycle through the rest of the filter time options, FO =O hour, F1 = 1 hour, F2 = 2 hours, F3 = 3 hours, F4 = 4 hours, and FC = 12 hours. Press the JETS pad again to exit the programming mode. During filtration, the low-speed pump will run and the blower (if installed) operates for 30 seconds at the start of the first filter cycle to clean out

the air channel. If a circulation pump is installed, when the water is at set temperature or below, it will run for 24 hours/day to constantly filter

the water. However, it turns off at 2F above the set temperature and comes back on for 1 hour every 3 hours until set temperature is reached again.

An ozone generator (if installed) also runs 24 hours/day.

Freeze Protection

If the high limit sensor detects 40F at the heater, then the high speed of pump 1 and pump 2 (if installed) automatically activates to provide freeze protection. The equipment stays activated until the sensor detects 45F at the heater. Freeze protection is activated regardless of the spa's status. In colder climates, an optional additional freeze sensor may be added to protect against freeze conditions. See your dealer for details.

Auxiliary Panel (optional)

The jets and blower (if installed) can also be activated from an auxiliary panel. The operation is the same as described for the main panel.

Diagnostic Messages

O H

Overheat Protection (Spa is deactivated)

DO NOT ENTER THE WATER. If the spa water has reached 112 F, remove

 

the spa cover to cool the water. Overheating may occur if the filter cycle

 

is set too long. At 110 F, the spa should reset itself. If the high limit sensor

 

detects 118 F at the heater, the spa will shut down. When the heater

 

cools to 110 F, press any button to reset the spa. If the spa will not

 

reset, then shut off power to the spa and call your dealer or service

 

organization.

FL

S n

Flow Switch Detection

Flashing alternately with temperature. The filter may need cleaning. The water level is too low. Be sure flow valves are open. FLO (NOT FLASHING) a pressure switch has malfunctioned. Contact your dealer or service organization.

Sensor (Spa is deactivated)

The high-limit sensor or water temperature sensor is not working. Call your dealer or service organization.