INSTALLATION

EBM Setup

The Powerware 9140 EBM comes with all hardware required for installation in a standard EIA or JIS seismic rack-mount configuration with square or round mounting holes. The rail assemblies adjust to mount in 19-inch panel racks from 24 to 30 inches deep.

Checking the EBM Accessory Kit

Verify that the following items are included with the EBM:

SMounting brackets and fasteners (if not already installed):

-(2) front mounting brackets

-(2) rear mounting brackets

-(12) M4 flat-head screws, plus (2) extra

SRails and fasteners:

-(2) sliding rail assemblies (left and right)

-(4) adapter plates (for 7.1 mm round hole)

-(4) adapter plates (for 9.5 mm square hole)

-(16) M5 machine screws, plus (2) extra

-(2) M6 machine screws, plus (2) extra

-(2) M6 clip nuts for racks with round holes, plus (2) extra

-(2) M6 cage nuts for racks with square holes, plus (2) extra

-(8) M4 machine screws with (8) M4 locknuts, plus (2) extra of each

SEBM user’s guide

SOptional seismic mounting brackets and fasteners:

-(2) EBM seismic mounting brackets

-(4) wing bolts, plus (1) extra

-(4) M6 machine screws

NOTE Discard the EBM user’s guide if you are installing the EBM with a new UPS at the same time. Use the UPS user’s guide instead to install both the UPS and the EBM.

EATON Powerware® 9140 EBM User’s Guide S 164201623 Rev A FINAL DRAFT 2006 July 14

17