Chapter 1 | Introduction |
The Extended Battery Module (EBM) can be added to the Powerware® 9140 uninterruptible power system (UPS) to extend the available battery time (see Table 1). Up to four EBMs can be installed with the Powerware 9140 UPS.
Table 1. Battery Runtimes (in Minutes)
Load | UPS Internal | +1 EBM | +2 EBMs | +3 EBMs | +4 EBMs |
|
(10 kVA Models) | Batteries |
| ||||
|
|
|
|
| ||
|
|
|
|
|
|
|
100% Load | 5 | 12 | 27 | 35 | 45 |
|
|
|
|
|
|
|
|
75% Load | 7 | 17 | 35 | 46 | 60 |
|
|
|
|
|
|
|
|
50% Load | 12 | 27 | 52 | 69 | 90 |
|
|
|
|
|
|
|
|
25% Load | 31 | 61 | 99 | 138 | 181 |
|
|
|
|
|
|
|
|
Load | UPS Internal | +1 EBM | +2 EBMs | +3 EBMs | +4 EBMs | |
(7.5 kVA Models) | Batteries | |||||
|
|
|
| |||
|
|
|
|
|
| |
100% Load | 8.5 | 23.5 | 37.5 | 53 | 65.5 | |
|
|
|
|
|
| |
75% Load | 12 | 30 | 52 | 69 | 86.5 | |
|
|
|
|
|
| |
50% Load | 22 | 51.5 | 78.5 | 98.5 | 111 | |
|
|
|
|
|
| |
25% Load | 48 | 94 | 116 | >120 | >180 | |
|
|
|
|
|
|
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
EATON Powerware® 9140 EBM User’s Guide S 164201623 Rev A FINAL DRAFT 2006 July 14 | 1 |