Eaton Electrical APR48, 10640205 Installation, Inspecting the Equipment and Reporting Damage

Models: 10640205 APR48

1 29
Download 29 pages 61.01 Kb
Page 14
Image 14

Data Power Solutions Quick Start Guide

Inspecting the Equipment and Reporting Damage

Unpack the APS dc power system and inspect it carefully for possible damage that may have occurred while in transit.

Next, check the equipment against the packing list (supplied with the equipment) and ensure that you have received the correct type of Access Power Rectifiers (either APR48 or APU48).

Report any damage or incorrect shipment immediately, using a completed Equipment Incident Report (at the back of this guide) to supply all relevant details. Fax the completed form to your local Eaton dc product representative.

Keep the original packaging. You will need it if any equipment needs to be returned to your local Eaton dc product representative.

Installation

Mounting the APS DC Power System

Location and Environment

APS dc power systems (rack-mounted and desktop versions) meet the safety and fire enclosure requirements (as specified in IEC 60950-1, UL 60950-1, EN 60950-1 and AS/NZS 60950.1).

Rack-Mounted Versions: APS3-05X and APS6-05X series dc power systems may be mounted in 19-inch wide host equipment racks (enclosed or open type) securely bolted to the floor.

Desktop Versions: APS3-06X series dc power systems may be positioned on any surface that supports the weight (12kg/26lb) of the power system.

The location must provide adequate airflow around the unit, (as per Clearance Requirements below) in an atmosphere free from excessive dust, corrosive fumes, or conductive contaminants.

Dust build-up within APS dc power systems may cause premature failure. In dusty environments, either install the power system in a sealed and air-conditioned equipment room, or provide fan assisted filtered air to create a positive pressure environment inside the equipment room. Both options require regular cleaning of the air filters.

Important Notes for Rack Mounted Systems

If this dc power system is installed in a closed or multi-unit rack assembly ensure that the ambient temperature is less than 40°C.

Ensure that the air flow is not restricted.

Ensure that the system's weight is adequately and evenly supported.

Take note of the maximum ac current stated on the nameplate. Ensure that the ac supply is correctly rated.

Ensure that reliable earthing is maintained. Carefully check earth continuity from the branch circuit to the dc power system.