Data Power Solutions Quick Start Guide
Step 3 – Terminate cable
•Terminate the positive battery cable at the Battery (+) terminal block.
•Terminate the negative battery cable at the Battery
•Tighten the terminal screws. Required torque: 2.5 - 3 Nm (22.1 – 26.5
Ensure that the polarity at the battery terminal blocks matches the polarity of the external battery. Connecting a reverse polarity battery to an APS dc power system will cause damage to the rectifier modules. Such damage will not be covered by the warranty.
16mm battery cable sleeve. | Battery cable clamp with posts removed. |
Step 4 – Arrange sleeve and clamp the battery cables
•Arrange the cable sleeve so that it is within 10mm (3/8”) of the terminals.
•Tighten the cable clamp screws. Required torque: 1.5 – 2Nm (13.2 – 17.7
Step 5 – Repeat for other battery cables (if required)
•Repeat the above procedure to connect up to three battery strings to an
Step 6 – Remove knockout and fit cover
•Remove the battery cable knockout(s) on the dc output cover:
Battery cable knockout.
•Remove any sharp edges, in particular the remaining
•Fit the dc output cover.