Data Power Solutions Quick Start Guide
Low Voltage Disconnect (if applicable)
Both the LVD disconnect and reconnect voltages are configurable. The default LVD disconnect voltage is set to 44V and the reconnect voltage to 48V. This hysteresis band ensures that the
Pre-Installation
Warnings
This section contains important warnings relating to:
•Inputs
•Equipment Classification
•Outputs
•Batteries (if applicable)
•Rectifiers
•Location and Environment
•Servicing
•EMC Compliance
Inputs
•Desktop Versions:
Pluggable Type A: Except for 120V input, if
•The maximum earth leakage current of each Access Power Rectifier is 1.5 mA. Ensure that any upstream Residual Current Devices (RCDs) are appropriately rated.
•The ac power cords (supplying the power system) must be suitably rated for the environment and ac power distribution system. In addition, these ac power cords must be approved and installed to comply with local wiring regulations.
•The earth conductor of each ac power cord must have a minimum cross sectional area of 1 mm2 (0.00155 in2).
•The maximum length of each ac power cord should not exceed 3m (10 feet), unless local wiring regulations permit otherwise.
•Ensure that the ac supply is disconnected from those fused ac power sockets before checking or replacing their respective fuses.
•Each socket, K1 to K3 (APS3), and K1 to K6 (APS6), contain two fuses, FS1 and FS2.
CAUTION:
•Use only 15 A, 250 VAC, 6.3 x 32 mm,