Data Power Solutions Quick Start Guide

Specifications

System Input

Input Voltage

APU48: L-N: 95-275V RMS

 

APR48: L-N: 185-275V RMS

 

 

 

 

Rated Input Current

 

 

 

@ 120V RMS with APU48 rectifiers:

APS3:

21A

(7A per ac power cord)

 

APS6:

42A

(7A per ac power cord)

@ 240V RMS with APU48 rectifiers:

APS3:

10.5A (3.5A per ac power cord)

 

APS6:

21A

(3.5A per ac power cord)

@ 208-240V RMS with APR48 rectifiers:

APS3:

24A

(8A per ac power cord)

 

APS6:

48A

(8A per ac power cord)

 

 

 

 

IEC AC Cord Sets

 

 

 

Cable

Cable rated according to AC voltage (refer

 

to the Rated Input Current values) and

 

local wiring regulations.

Connector 1 (AC supply)

Refer to the Rated Input Current values

 

according to AC voltage.

Connector 2 (Data Power Solution)

IEC type C-13

 

 

 

 

Frequency Range

45-66Hz

 

 

 

 

Maximum Earth Leakage Current

1.5mA (per Access Power Rectifier)

System Output

Output Voltage (nominal)

48V

 

Output Power (maximum)

 

 

APS3-058 and APS3-060:

2.16kW with 3 APU48 rectifiers

 

4.50kW with 3 APR48 rectifiers

APS3-059 and APS3-061:

1.70kW with 3 APU48 rectifiers

 

3.00kW with 3 APR48 rectifiers

APS6-058:

4.32kW with 6 APU48 rectifiers

 

9.00kW with 6

APR48 rectifiers

APS6-059:

3.40kW with 6

APU48 rectifiers

 

7.10kW with 6

APR48 rectifiers

 

 

 

Environment

Ambient Temperature Range (operating)

-10°C to +40°C [+14°F to 104°F]

Relative Humidity (operating and storage)

<95% (non condensing)

28

Copyright © 2006-2009 Eaton Corporation. All Rights Reserved.