Intelligent Technologies (IT.) D77A I/O Module Products

Analog Input Modules

Figure 20 illustrates the basic signal processing operation. Analog signals from four separate channels are received by a multiplexer (MUX). The MUX sequentially transfers this data to an analog-to-digital converter (ADC). The ADC measures the analog signal and converts it to a digital value. This digital value is presented to the controller’s central processes unit (CPU). This data is then presented to the QCPort for external processing.

V0

 

 

 

 

 

I0

 

 

 

 

 

V1

M

 

 

 

 

 

 

 

 

 

I1

U

 

ADC

CPU

QC Port

V2

X

 

 

 

 

 

 

 

 

 

I2

 

 

 

 

 

V3

 

 

 

 

 

I3

 

 

 

 

 

C0

 

 

 

 

 

C1

V1

+V2

-V2

 

 

 

 

 

 

 

C2

 

 

 

 

 

C3

 

 

 

 

 

 

 

 

 

 

SCHEM-001

Figure 20: Analog Input Module Operation

Analog input signal delays are associated with multiplexer switching, channel updating and channel reconfiguration. These delays are all influenced by analog input filter frequency selection.

Table 24: Analog Input Signal Delays

Filter Setting

Total Update Time

 

 

 

 

50 Hz

336 ms

 

 

60Hz

283.2 ms

 

 

250 Hz

80 ms

 

 

500 Hz

44 ms

 

 

MN05002001E

For more information visit: www.EatonElectrical.com