Intelligent Technologies (IT.) D77A I/O Module Products

MN05002001E For more information visit: www.EatonElectrical.com 43

Analog Outputs

Analog signals are typically used to transmit or indicate linear data like pressure or linear actuation, as illustrated in Figure 41. The

analog output devices to which analog outputs are wired are typically current loop or voltage range devices like 4-20 mA signals or

0-10V signals. Refer to Analog Output Module Specifications on page16 for module details.

Note: Ground the shield on one end only. It is recommended to limit the cable impedance by keeping the cable length as short as

possible. Limiting the distance from ground to the shield is also recommended. The recommended cable is a BeldenTM 8761 or

equivalent.

Figure 41: Analog Output Wiring

a) Control Transformer

b) 24 VDC Power Supply

c) Voltage Output Device

d) Current Output Device

Wire Type Wire Size Terminal Torque

Solid Cu-90°C #14 - # 22 AWG 4.5 in-lbs.

Stranded Cu-90°C #16 - # 22 AWG 4.5 in-lbs.

H1 H4
H3 H2
24VDC
10FU
1
2
3
4
5
6
7
8
I0
C0
V1
I1
C1
NC
NC
9
10
11
12
-
X1 X2
120VAC NEU
+
-
+
JIC-0008
NC
NC
V0
V
I
a
b
c
d
e
-
+