Raven Installation Guide Servo Control Operation
MAN-RAVIG (Ver. 1.1)
4-5
4.8 Status Indications
The following table lists the Raven amplifier status indications.
Function
Latch
Option
AOK
SO1
SO2
SO3
1 Amplifier OK
(AOK)
N/A Low Open collector Open collector Open collector
2 External disable No Low Low Open collector Low
3 Current limit No Low Open collector Open collector Low
4 Short Yes Open collector Low Open collector Low
5 Over
temperature
Yes Open collector Open collector Low Low
6 Internal supplies
protection
No Open collector Low Low Open collector
7 Under voltage No Open collector Low Open collector Open collector
8 Over voltage No Open collector Open collector Low Open collector
9 Shunt* No Low Open collector Low Open collector
10 Power Up Reset No Open collector Open collector Open collector Open collector
* This indication can be used as a digital input for activating an external shunt regulator.

Table 4-3: Raven Status Indications

Notes:
Without latch mode:
The status indications are reset when the fault disappears.
With latch mode:
The Short and Over Temperature Failure status indications are reset when the
enable signal is temporarily removed from the enable input.
Multiple faults:
Only the reading of the first fault is reliable. Additional faults add on to the
status outputs and the indication is therefore meaningless.