Section 3 • Hardware Architecture
High Level Shutdown Input:
•This input must be energized in order for the com- pressor to operate. If
Oil Level Float Switch #1 Input:
•Used for Cool Compression. Oil Level Float Switch #2 Input:
•Used for Cool Compression. Remote Select #1/#2 Input:
•This input enables or disables remote I/O control. Energizing this input enables the Remote Capacity Increase and Remote Capacity Decrease inputs.
Remote Start/Stop Input:
•If the compressor is enabled for remote I/O control, this input is enabled. Energizing this input will issue a start for the compressor as long as it is available to run.
Remote Capacity Increase Input:
NOTE
The scan interval on the remote increase and decrease inputs is approximately ONE SECOND. Please take that into account when developing a control scheme using the remote increase and remote decrease inputs for compressor control.
•If the compressor is enabled for remote I/O control, this input is enabled. Operational only when the com- pressor is running. Energizing this input will increase the slide valve position.
•The slide valve will continuously increase as long as this input is energized. The slide valve will not in- crease when this input is
Remote Capacity Decrease Input:
•Operational only when the compressor is running. This input is enabled if the compressor is enabled for remote I/O control. Energizing this input will de- crease the slide valve position. The slide valve will continuously decrease as long as this input is ener- gized. The slide valve will not decrease when this in- put is
Condenser Step #1 Output:
•This output is enabled when condenser control op- tion is selected. A condenser fan or pump will be turned on or off by this output.
Condenser Step #2 Output:
•This output is enabled when condenser control op- tion is selected. A condenser fan or pump will be turned on or off by this output.
Condenser Step #3 Output:
•This output is enabled when condenser control op- tion is selected. A condenser fan or pump will be turned on or off by this output.
Condenser Step #4 Output:
•This output is enabled when condenser control op- tion is selected. A condenser fan or pump will be turned on or off by this output.
Auxiliary Inputs #1 - #8:
•Optional inputs that can be configured as an alarm or trip. Typically connected to external switched devices.
Auxiliary Outputs #1 - #4:
•Optional inputs that can be configured as an alarm or trip. Typically connected to external switched devices.
Analog Inputs
Refer to Table 2-2. Analog Inputs.
Motor Current:
•Default is a
Suction Pressure:
•Default signal is
Discharge Pressure
•Default signal is
Oil Filter Inlet Pressure:
•Default signal is
Oil Manifold Pressure:
•Default signal is
Economizer Pressure:
•Default signal is
Slide Valve Position:
•Reads the
3 – 4 | Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153 |