Emerson 20/20 service manual Step Control

Models: 20/20

1 120
Download 120 pages 9.8 Kb
Page 62
Image 62

Section 11 • Condenser Control

Condenser Press:

This is the read only parameter and it displays the present value of condenser pressure.

Condenser Setpoint:

This is the condenser pressure setpoint that needs to be maintained.

Upper Deadband:

This is the condenser pressure setpoint upper dead- band value. No additional condenser capacity is add- ed when the condenser is selected for automatic step control and the condenser pressure falls within this deadband.

Lower Deadband:

This is the condenser pressure setpoint lower dead- band value. Condenser capacity is not reduced when the condenser is selected for automatic step control and the condenser pressure falls within this deadband.

Ambient Temp:

This is the read only parameter and it displays the present value of ambient temperature. This is dis- played only when Ambient Sensor is enabled from Configuration Screen.

Wetbulb Temp:

This is the read only parameter and it displays the present value of wetbulb temperature. This is dis- played only when Wetbulb Sensor is enabled from Configuration Screen.

Wetbulb Offset:

This is the offset value from wetbulb temperature as the override point.

Switch Temp:

This is the ambient temperature setpoint used for au- tomatic switching of profile from summer to winter and vice-versa.

Profile Selection:

Profile selection allows operator to have two different output profiles for summer and winter. Operator can have different selection of fans, pumps & VFD in five steps of step control table. Different profiles allow inclusion/exclusion of water pumps in cold weather when summer/winter auto switch is enabled. This selection is inactive when Run mode is Auto and Summer/Winter Auto Switch is enabled.

High to Low Speed Fan Delay:

This is a time delay for the fan spin down in case of 2- speed motor/dual speed fan.

Summer/Winter Auto Switch:

This checkbox when enabled allows profiles to switch automatically depending on ambient temperature setpoint when Run Mode is “Auto”. When ambient temperature falls below ambient temperature set- point, winter profile is used. Similarly when ambient temperature is above ambient temperature setpoint, summer profile is used.

Wetbulb Override:

This checkbox when enabled gives the operator a functionality to control energy wastage. When the condenser temperature reaches wetbulb tempera- ture plus the operator given offset, then the con- denser control operation does not add additional steps. This is done as it is not possible to lower the temperature anymore, and by adding more fans or pumps controls the operation by manually stepping using an on/off toggle button at each step.

Step Control

The Step Control allows the operator to setup the man- ner in which Fans, Pumps & VFD will be turned on/off. Fans & Pumps are connected on digital outputs Out #1 to Out #4. VFD Fan is connected on Analog Output. Each step can have maximum of five outputs connected to it. Each step can be opted in or out depending on enabling of checkbox, see Figure 11-2. Step Control Screen.

When Run Mode is Auto and condenser pressure rises above upper deadband, condenser step gets incremen- tal from Step 1 to Step 5 and hence switching on/off Pumps, Fans & VFD connected on outputs. This holds true for decremented of steps from Step 5 to Step 1 when condenser pressure falls below lower deadband.

Step Delay:

Allows operator to set time delays between condens- er steps. Condenser Pressure must be outside upper or lower deadband continuously for delay time in or- der to increase or decrease condenser steps. While in a VFD step, an additional step can only be added once VFD has reached its maximum speed setpoint and the delay timers are satisfied.

Similarly in a VFD step, a step can only be removed once VFD has reached its minimum speed setpoint and the delay timers are satisfied. Step Delay acts as “ON” timer while loading and acts as “OFF” timer while unloading for the same step.

Low Speed Fan:

Allows steps to have option for time delay in case of fan spin down. Any of Out #1 to Out #4 can be

11 – 2

Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153

Page 62
Image 62
Emerson 20/20 service manual Step Control

20/20 specifications

Emerson 20/20 is an advanced platform designed for real-time data analytics, visualization, and operational optimization in industrial settings. This robust solution aims to empower organizations by providing actionable insights derived from their operational data, enabling enhanced decision-making and improved efficiency.

One of the standout features of Emerson 20/20 is its ability to integrate seamlessly with various sources of data, whether structured or unstructured. It consolidates information from different systems, such as historians, control systems, and ERP software, allowing users to gain a comprehensive view of their operations. This integration capability is crucial for businesses looking to maximize their data utilization without being confined to a single data source.

The platform employs powerful analytics tools that utilize machine learning and artificial intelligence technologies. These tools are designed to automatically identify patterns, anomalies, and trends in real-time. By leveraging predictive analytics, Emerson 20/20 helps organizations forecast potential issues before they escalate, allowing for proactive maintenance and minimizing downtime.

Emerson 20/20 also features user-friendly visualization dashboards, which provide customizable views tailored to individual user roles. This means that whether you are a plant manager, a process engineer, or an executive, you can access relevant data that speaks directly to your needs. These dashboards facilitate easier understanding of complex data sets, promoting informed decision-making across the organization.

One notable characteristic of Emerson 20/20 is its adaptability and scalability. Businesses of all sizes can implement the platform and scale its features according to their needs. This flexibility ensures that both small operations and large enterprises can derive value from the solution, making it an attractive option for various industries.

Additionally, the platform is designed with cybersecurity in mind, ensuring that data integrity and confidentiality are maintained. This aspect is increasingly important as industries become more interconnected and target more sophisticated cyber threats.

In summary, Emerson 20/20 stands out as a powerful tool for organizations seeking to harness their operational data effectively. With its advanced analytics capabilities, seamless integration, customizable visualization, and scalable design, it offers a comprehensive solution to optimize industrial performance and support data-driven decision-making. As businesses continue to navigate the complexities of modern operations, Emerson 20/20 provides the insights necessary to stay competitive and responsive to changing market demands.