Communication
6.0COMMUNICATION
6.1
The UPS has a
When power is interrupted and battery power is low, Liebert MultiLink software can signal the host computer to gracefully shut down the operating system.
Table 4 |
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| Assignment Description | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
1 |
|
|
| Low Battery (open collector) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
2 |
|
|
| UPS TxD (not used) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
3 |
|
|
| UPS RxD (not used) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||
4 |
|
|
| Remote Shutdown |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
5 |
|
|
| Common |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| |||
6 |
|
|
| Output Off, (short to Pin 5, | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
7 |
|
|
| Low Battery (open emitter) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
8 |
|
|
| Utility Fail (open emitter) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
9 |
|
|
| Utility Fail (open collector) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| |||||
| Pin Assignment |
|
| Collector to Emitter* |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 6 | 7 |
| 8 | 9 |
|
|
|
|
| (+) | Open |
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| Collector |
| |
|
|
|
|
|
|
|
| 330 Ohms |
| ||||
|
|
|
|
|
|
|
|
|
|
| |||
1 | 2 | 3 | 4 | 5 |
|
|
| Open |
| ||||
|
|
|
|
|
| Emitter |
| ||||||
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6.2Remote Shutdown Via the
The Liebert PSI XR can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB-
9 connector.
6.2.1Any Mode Shutdown Via Pins 5 & 6
When Pin 6 is shorted to Pin 5, the UPS output is shut Off no matter what mode the UPS is operating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS output can be enabled by pressing the ON/Alarm Silence/Manual
6.2.2Battery Mode Shutdown Via Pins 4 & 5
While the UPS is operating on battery, a
After Pin 4 receives the shutdown signal, a
6.3Network Surge Protection Connectors
Network (in and out) connectors on the rear of the UPS provide transient voltage surge suppression (TVSS) for network devices.