Emerson 1500, 3000, 1000, 2200 Table, Liebert PSI XR battery run times continued, Specifications

Models: 1000 1500 2200 3000

1 32
Download 32 pages 13.16 Kb
Page 29
Image 29
Liebert PSI XR battery run times (continued)

 

 

 

 

 

 

Specifications

Table 8

Liebert PSI XR battery run times (continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of Batteries

Load %

1000

1500

2200

 

3000

 

 

10

790

627

483

 

330

 

 

 

 

 

 

 

 

 

 

20

494

371

303

 

204

 

 

 

 

 

 

 

 

 

 

30

360

264

221

 

148

 

 

 

 

 

 

 

 

 

 

40

283

204

174

 

116

Internal battery

 

 

 

 

 

 

50

233

167

143

 

95

+ 4 External

 

 

 

 

 

 

60

198

141

122

 

76

Battery Cabinets

 

 

 

70

172

122

106

 

66

 

 

 

 

 

 

 

 

 

 

80

152

108

94

 

59

 

 

 

 

 

 

 

 

 

 

90

137

96

79

 

52

 

 

 

 

 

 

 

 

 

 

100

124

82

72

 

48

 

 

10

965

762

564

 

392

 

 

 

 

 

 

 

 

 

 

20

605

452

354

 

243

 

 

 

 

 

 

 

 

 

 

30

440

320

258

 

176

 

 

 

 

 

 

 

 

 

 

40

346

248

203

 

138

Internal battery

 

 

 

 

 

 

50

265

203

167

 

113

+ 5 External

 

 

 

 

 

 

60

242

171

142

 

96

Battery Cabinets

 

 

 

70

211

148

124

 

79

 

 

 

 

 

 

 

 

 

 

80

186

131

110

 

70

 

 

 

 

 

 

 

 

 

 

90

167

117

98

 

62

 

 

 

 

 

 

 

 

 

 

100

151

106

84

 

56

 

 

10

1140

897

644

 

454

 

 

 

 

 

 

 

 

 

 

20

714

531

405

 

281

 

 

 

 

 

 

 

 

 

 

30

520

377

295

 

204

 

 

 

 

 

 

 

 

 

 

40

408

292

232

 

160

Internal battery

 

 

 

 

 

 

50

337

239

191

 

131

+ 6 External

 

 

 

 

 

 

60

286

202

163

 

112

Battery Cabinets

 

 

 

70

249

175

142

 

97

 

 

 

 

 

 

 

 

 

 

80

220

154

125

 

81

 

 

 

 

 

 

 

 

 

 

90

197

138

112

 

72

 

 

 

 

 

 

 

 

 

 

100

179

124

102

 

65

 

 

 

 

 

 

 

 

Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.

25

Page 29
Image 29
Emerson 1500, 3000, 1000, 2200 user manual Table, Liebert PSI XR battery run times continued, Specifications