Specifications
8.0SPECIFICATIONS
Table 6 | Liebert PSI XR specifications |
|
|
|
| |
|
|
|
|
|
|
|
| Model Number |
| ||||
| PS1000RT3120XRW | PS1500RT3120XRW | PS2200RT3120XRW | PS3000RT3120XRW | ||
|
| |||||
Power Rating, VA/W | 1000VA/900W |
| 1500VA/1350W | 1920VA/1920W* | 3000VA/2700W | |
Dimensions, W x D x H, in (mm) |
|
|
|
| ||
| Unit | 17.3 x 19.3 x 3.5 (440 x 490.5 x 88) | 17.3 x 27.6 x 3.5 (440 x 700.5 x 88) | |||
| Shipping | 22 x 24.1 x 9 (560 x 612 x 228) | 22 x 34.8 x 9.0 (560 x 884 x 228) | |||
Weight, lb (kg) |
|
|
|
|
| |
| Unit | 56 (25) |
| 62 (28) | 92 (42) | 105 (48) |
| Shipping | 64 (29) |
| 70 (32) | 101 (46) | 115 (52) |
Input AC Parameters |
|
|
|
|
| |
| Surge Protection |
|
|
| 570J |
|
| Voltage Range |
|
|
| ||
Without Battery Operation |
|
|
| |||
|
|
|
|
| ||
| Frequency Range |
|
| 45~65Hz, (±0.5Hz) |
| |
| Input Power Cord, | NEMA | NEMA | NEMA | ||
| 10ft (3m) attached | |||||
|
|
|
|
|
| |
|
|
|
|
| (4) NEMA | (4) NEMA |
|
|
|
|
| (2) NEMA | |
| Output Receptacles | (6) NEMA | (2) NEMA | |||
|
|
|
|
| accepts15A Plug | accepts15A Plug |
|
|
|
|
| (1) NEMA | |
|
|
|
|
|
| |
| Voltage (Normal Mode) |
|
| 110/120/127 | VAC (configurable) |
|
| Voltage (Battery Mode) |
| 110/120/127 VAC; ±5% before | |||
| Transfer Time |
|
|
| ||
| Waveform |
|
| Sinewave |
| |
Battery Parameters |
|
|
|
|
| |
| Type |
|
|
| ||
| Quantity x Voltage x Ah | 4 x 12 x 7.2 |
| 4 x 12 x 9 | 8 x 12 x 7.2 | 8 x 12 x 9 |
| Recharge Time | 5 hours to | 90% of rated capacity, | after full discharge into | resistive load | |
Battery Backup Time |
|
|
|
|
| |
| Full Load |
|
| 5 minutes |
| |
| Half Load |
|
| 10 minutes |
| |
Environmental |
|
|
|
|
| |
Operating Temperature, °F (°C) |
|
| 32 to 104 (0 to 40) |
| ||
Storage Temperature, °F (°C) |
|
| 5 to 104 |
| ||
| Relative Humidity |
|
| 0% to 90%, |
| |
| Operating Altitude |
|
| Up to 10,000 ft (3000m) |
| |
| Audible Noise |
|
| <45 dBA |
| |
Agency |
|
|
|
|
|
|
| Safety |
|
| UL 1778, |
| |
| Surge |
|
| ANSI C62.41 CatA Lev3 (surges) | ||
| ESD |
|
|
| ||
| Susceptibility |
|
|
| ||
Electrical Fast Transient |
|
|
| |||
| Emissions |
|
| FCC Part 15, Class A |
| |
| Conducted Immunity |
|
|
| ||
| Harmonics |
|
|
| ||
| Network surge |
|
| UL 497 B |
| |
| Transportation |
|
| ISTA Procedure 1A Certification |
| |
| Environmental |
|
| ROHS compliant |
| |
|
|
|
|
|
| |
|
|
|
|
|
|
|
*NEC limits the input current rating of the
22