Appendix A Reference Data

Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . .page A-1
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .page A-3
Performan c e Specific at io ns . . . . . . . . . . . . . . . . . . . . . . . page A-4
Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-4
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-8
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-12

FUNCTIONAL

SPECIFICATIONS Inputs
Eight independently configurable channels including combinations of 2- and
3-wire RTDs, thermocouples, mV, 2- and 3-wire and ohm inputs.
4–20 mA inputs using optional connector(s).
Outputs
Manchester-encoded dig ital signa l that conforms to IEC 61158 and ISA 50 .02.
Status
600 Vdc channel to channel isolation(1)
10 Vdc channel to channel isolation for all operating conditions with
maximum 150 m. (500 ft) of sensor lead length 18 AWG.
Ambient Temperature Limits
–40 to 185 °F (–40 to 85 °C)
Isolation
Isolation between all sensor channels is rated to 10Vdc over all operating
conditions. No damage will occur to the device with up to 600 Vdc between
any sensor channel.
Power Supply
Powered over FOUNDATION fieldbus with standard fieldbus power supplies.
The transmit te r op er at es be tween 9.0 and 32.0 V dc, 22 mA maximu m .
(Transmitter po we r te rm ina ls ar e ra te d to 42.4 V dc.)
(1) Reference conditions are -40 to 60 °C (-40 to 140 °F) with 30 m. (100 ft) of sensor lead
length 18 AWG wire.