COMMUNICATIONS

Communications Interface Port

The Liebert GXT2U UPS has a standard DB-9 serial port female connector located on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:

Pin

 

 

 

 

Assignment Description

 

 

1

 

Low Battery (open collector)

 

 

2

 

UPS TxD (typical RS-232 levels)

 

 

3

 

UPS RxD (typical RS-232 levels)

 

 

4

 

Remote Shutdown (5-12VDC, 10-24 mA max); battery operation

 

5

 

Common

 

 

 

 

 

 

 

6

 

Remote Shutdown (short to pin 5); all modes of operation

 

 

7

 

Low Battery (open emitter)

 

 

8

 

Utility Fail (open emitter)

 

 

9

 

Utility Fail (open collector)

 

 

 

 

 

 

 

 

 

 

 

Pin Assignment

 

Collector to Emitter*

 

 

 

 

 

 

 

 

 

 

 

6

7

8

9

 

 

 

 

(+)

Open

 

 

 

 

 

 

 

 

 

 

 

 

 

Collector

 

 

 

 

 

 

330 Ohms

 

 

 

 

 

 

 

 

1

 

2

3

4

5

 

 

 

(-)

Open

 

 

 

 

 

Emitter

 

 

 

 

 

* Maximum voltage and current on pins 1, 7, 8, and 9 is 60VDC; 10.0 mA.

Pins 4 & 5 - Remote Shutdown on Battery

1.This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the utility, Pin 4 will ignore any signal on this pin.

2.Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using Liebert’s contact closure cable. It cannot be used with just a contact closure unless the relay is used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shut- down signal for 1.5 seconds, the command cannot be canceled.

3.A battery shutdown signal on Pin 4 will NOT cause an immediate shut- down. A shutdown signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will shut down.

4.If the utility returns during the 2-minute timer countdown, the shutdown timer will continue until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10 seconds even if AC input power returns before the UPS turns OFF. This serves to reset and restart the server.

Whether the UPS turns back ON when power is restored depends on the auto- restart setting: enabled or disabled.

If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown delay.

19

Page 23
Image 23
Emerson GXT2U Communications Interface Port, Pins 4 & 5 Remote Shutdown on Battery, Pin Assignment Description