| SPECIFICATIONS |
Model Number | |
Model Rating | 2700VA/1890W |
DIMENSIONS: in. (mm) |
|
Unit - W x D x H: in. (mm) | 3.5 x 24.2 x 17 (87 x 618 x 430) |
Shipping - W x D x H: in. (mm) | 10.5 x 27.2 x 23 (268 x 692 x 585) |
WEIGHT lbs (kg) |
|
Unit: lbs (kg) | 75.2 (34.1) |
Shipping: lbs (kg) | 84.9 (38.5) |
INPUT AC PARAMETERS |
|
Voltage Range (typical) | 208 VAC nominal; variable based on output load |
100% - 90% loading | 176 VAC/280 VAC |
90% - 70% loading | 159 VAC/280 VAC |
70% - 30% loading | 139 VAC/280 VAC |
30% - 0% loading | 119 VAC/280 VAC |
Frequency | 40 - 70 Hz; Auto Sensing |
Input Power Cord | 10 ft. attached w/ NEMA |
OUTPUT AC PARAMETERS |
|
Output Receptacles | (2) NEMA |
(1) NEMA | |
Voltage | 200/208/220/230/240 (user configurable) VAC; ±3% |
Frequency | 50 Hz or 60 Hz |
Waveform | Sinewave |
Main Mode Overload | 200% for 8 cycles; 130% for 10 seconds with transfer to |
| bypass |
BATTERY PARAMETERS |
|
Type | |
Qty x V x Rating | 6 x 12V x 9.0 AH |
Battery Mfg/Part # | Panasonic/ |
Yuasa/ REW | |
See Battery Run Times charts | |
Recharge Time | 5 Hours to 95% capacity after full discharge into 100% load |
(Internal Batteries Only) | |
ENVIRONMENTAL |
|
Operating Temp | +32°F to +104°F (0°C to +40°C) |
Storage Temp | +5°F to +122°F |
Relative Humidity | 0% to 95%, |
Operating Elevation | Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating |
Storage Elevation | 50,000 ft. (15,000 m) maximum |
Audible Noise | <55 dBA, at 1 meter from the rear |
| <50 dBA, at 1 meter from the front or sides |
AGENCY |
|
Safety | UL 1778, |
RFI/EMI | FCC Part 15, Subpart B, Class A |
Surge Immunity | IEEE 587 Category A & B |
Transportation | ISTA Procedure 1A |
29