Emerson GXT 10KVA user manual Electrical connections-non-transformer model MBC

Models: GXT 10KVA

1 32
Download 32 pages 28.08 Kb
Page 21
Image 21

Cable Installation

Figure 10 Electrical connections—non-transformer model MBC

Common Ground

Wire Connection Torque

Value: 13 in-lbs

Common Ground

Wire Connection Torque

Value: 120 in-lbs

TB3 UPS Input Terminal

Block

Wire Connection Torque

Value: 28 in-lbs

TB1 Maintenance Bypass Terminal

Block

Wire Connection Torque

Value: 50 in-lbs

Common Ground

Wire Connection

Torque Value: 120 in-lbs

120V

240V 208V

120V

Common Ground

Wire Connection Torque

Value: 120 in-lbs

TB5 Hardwire Output Terminal

Block

Wire Connection Torque

Value: 35 in-lbs

Wire Connection Torque

Value: 120 in-lbs

TB4 UPS Output Terminal

Block

Wire Connection Torque

Value: 28 in-lbs

TB2 Maintenance Bypass

Terminal Block

Wire Connection Torque

Value: 50 in-lbs