Specifications

9.0SPECIFICATIONS

General & Environmental

Rating

 

 

 

 

 

 

 

 

 

 

 

 

kVA

Models NMB1x and NMB4x = 18

 

 

 

 

 

 

 

 

 

Unit Rating

Models NMB5x and NMB8x = 20

 

 

 

 

 

 

 

 

 

 

 

Amps

Models NMB1x and NMB4x = 100 max

 

 

 

 

 

 

 

 

 

 

 

 

Models NMB5x and NMB8x = 125 max

 

 

 

 

 

 

 

 

 

Safety Standards

 

 

 

UL 1778, c-UL

 

 

 

 

 

 

 

 

 

 

Mechanical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

 

 

 

9.5 (241)

 

 

 

 

 

 

 

 

 

 

 

Depth

In (mm)

 

 

26.5 (700)

 

 

Dimensions

 

 

 

 

 

 

 

Height

 

 

 

30.4 (775)

 

 

 

 

 

 

 

 

 

 

Weight

lb (kg)

287 (130)

 

 

85 (39)

 

transformer model

 

transformerless model

 

 

 

 

Environmental

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Temperature (max)

F (C)

 

32º - 104º (0º - 40º)

 

 

 

 

 

 

 

Relative Humidity

%

 

0-95% non-condensing

 

 

 

 

 

 

 

 

Maximum Operating Altitude

Ft (M)

 

 

10,000 (3000)

 

 

 

 

 

 

 

 

 

 

 

Input Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Input Voltage

VAC

 

 

 

208 or 240

 

 

 

 

 

 

 

 

Input Frequency (nominal)

Hz

 

 

60

 

 

 

 

 

 

 

 

 

Input Frequency Range

Hz

 

 

55-65

 

 

 

 

 

 

 

 

 

 

 

Output Data

 

 

208/240

 

 

240

 

208

 

 

 

 

 

 

 

Output Voltage

VAC

120/120/208/240

 

120/120/240*

 

120/120/208*

 

 

 

 

 

 

 

Transfer Time

msec

 

<4 msec typical

 

 

 

 

 

 

 

 

Output Frequency

Hz

 

 

60

 

 

 

 

 

 

 

 

 

 

 

* Transformerless model requires neutral input