Cable Installation

Figure 12 Connecting Nfinity to Maintenance Bypass without transformer

Input 2

Input 1

 

 

 

 

120

120

 

 

 

 

208

TB2

NFINITY MAINTENANCE BYPASS CABINET

TB5

240

 

L1

 

WITHOUT TRANSFORMER

 

1

 

L2

 

 

 

2

 

N

 

 

 

3

 

 

 

 

 

4

 

G

Remove these three

 

 

 

TB1

wires for dual source

 

G

 

(see NOTE below)

 

 

L1

 

 

 

 

 

 

 

 

L2

 

 

 

G

 

N

 

 

 

G

 

 

 

 

 

 

G

TB3

 

TB4

 

 

L1 L2

G

1 2 3

4

 

 

 

Flexible conduit

L1 L2

TB1

Ensure that the tap selector is set to the correct input voltage

G1 2 3

TB2

NFINITY UPS

1 2 3 4 5

TB3

GEC

See Nfinity user manual for details on connecting GEC.

NOTE

1.SINGLE-SOURCEFEED—If feeding the Maintenance Bypass Cabinet from a single source, the input connection may be made to either TB1 or TB2.

2.DUAL-SOURCEFEED—If feeding the Maintenance Bypass Cabinet from a dual source, the UPS input supply connection must be made to TB1 and the bypass input supply connection must be made to TB2. The jumpers between TB1 and TB2 must be removed.

3.If connected equipment is a combination of 208 VAC and 120 VAC, use a three-phase panel board connected to the output terminal TB5.