7
HARDWIRE CONNECTIONS

Electrical Installation Considerations

The front and bottom of the POD provide alternate conduit entry
points for both the UTILITY and LOAD connections.
Figure 5 Conduit entry
!CAUTION
This UPS must be installed by competent electrical
personnel and wired in accordance with local/national
electrical codes.
!CAUTION
The utility input supply to the POD must be protected by a
branch rated circuit breaker. The UPS output must also be
protected with a circuit breaker connected to the load, rated
to carry the input current, and be capable of breaking the
maximum expected short circuit current of this branch
circuit. The breaker is to be mounted within 6 feet of the
POD and be readily accessible to the operator. Refer to
Table 1 for breaker specification.
!CAUTION
Before installing, open all branch circuit power at the
nearest disconnect, turn UPS off, and disconnect all cords to
and from the UPS.
UPS
AVAILABLE
UPS
UPS
UTILITY
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
IF UTILITY LAMP IS ILLUMINATED
MAINTENANCE BYPASS POSITION
MAY BE SELECTED
SWITCH TO UPS POSITION ONLY
WHEN UPS LAMP IS ILLUMINATED
CAUTION
LOAD UTILITY
FRONT VIEW
BOTTOM VIEW
Conduit Entry Knockouts