HARDWIRE CONNECTIONS

Electrical Installation Considerations

! CAUTION

This UPS must be installed by competent electrical personnel and wired in accordance with local/national electrical codes.

! CAUTION

The utility input supply to the POD must be protected by a branch rated circuit breaker. The UPS output must also be protected with a circuit breaker connected to the load, rated to carry the input current, and be capable of breaking the maximum expected short circuit current of this branch circuit. The breaker is to be mounted within 6 feet of the POD and be readily accessible to the operator. Refer to Table 1 for breaker specification.

! CAUTION

Before installing, open all branch circuit power at the nearest disconnect, turn UPS off, and disconnect all cords to and from the UPS.

The front and bottom of the POD provide alternate conduit entry points for both the UTILITY and LOAD connections.

Figure 5 Conduit entry

FRONT VIEW

LOAD

CAUTION

IF UTILITY LAMP IS ILLUMINATED

MAINTENANCE BYPASS POSITION

 

MAY BE SELECTED

 

SWITCH TO UPS POSITION ONLY

 

WHEN UPS LAMP IS ILLUMINATED

UPS

MAINTENANCE BYPASS

UPS

AVAILABLE

AVAILABLE

 

UPS

UTILITY

 

UTILITY

CONNECT UPS

LINE CORD HERE

Conduit Entry Knockouts

BOTTOM VIEW

7

Page 11
Image 11
Emerson MP2-115HW user manual Electrical Installation Considerations, Hardwire Connections