START EQUIPMENT
1.Turn on all loads hardwired to the output of the POD. The 2U POD now powers your equipment in the UTILITY mode.
2.Turn ON the loads and ensure all are up and operating properly.
3.Start the UPS according to its specific user manual.
4.Verify that the UPS lamp (green) on the 2U POD is illuminated. If so, transfer the rotary switch from UTILITY to UPS. The load is now being supplied with conditioned power through the UPS.
5.Before any operation or procedure, always verify that both the UPS lamp (green) and the UTILITY lamp (amber) are illuminated before changing the status of the rotary switch.