TROUBLESHOOTING

Problem

Cause

Solution

 

 

 

 

UTILITY not present.

Call qualified service personnel

 

to restore power.

 

 

 

 

 

 

Utility Branch Circuit

Verify that the branch circuit

 

Breaker may be

 

breaker is closed.

UTILITY lamp

open.

 

(amber)

 

 

 

 

not illuminated.

 

Refer to 2U Hardwire POD

 

2U Hardwire POD

installation instructions in this

 

input power not

manual:

 

connected to

Installation on GXT 2U UPS

 

UTILITY.

and

 

 

Rack Mount Installation.

 

 

 

 

UPS output power

Turn on UPS. Refer to UPS user

 

not present.

manual.

UPS Available

 

 

 

Refer to 2U Hardwire POD

lamp (green)

UPS input and/or

installation instructions in this

not illuminated.

output cord not

manual:

 

connected to 2U

Installation on GXT 2U UPS

 

Hardwire POD.

and

 

 

Rack Mount Installation.

 

 

 

2U Hardwire

 

Verify that utility and UPS are

POD will not

 

Input power cannot

on, all circuit protectors are

start some / all

support load.

closed, and load is within the

connected

 

rating of the power source.

loads.

 

 

 

 

 

 

Utility or UPS

Overcurrent

 

circuit

protection on 2U

Recalculate load requirements.

protectors trip

Hardwire POD

after resetting.

connected load.

 

 

 

 