TROUBLESHOOTING
Problem | Cause | Solution | |
|
|
| |
| UTILITY not present. | Call qualified service personnel | |
| to restore power. | ||
|
| ||
|
|
| |
| Utility Branch Circuit | Verify that the branch circuit | |
| Breaker may be | ||
| breaker is closed. | ||
UTILITY lamp | open. | ||
| |||
(amber) |
|
| |
|
| ||
not illuminated. |
| Refer to 2U Hardwire POD | |
| 2U Hardwire POD | installation instructions in this | |
| input power not | manual: | |
| connected to | • Installation on GXT 2U UPS | |
| UTILITY. | and | |
|
| • Rack Mount Installation. | |
|
|
| |
| UPS output power | Turn on UPS. Refer to UPS user | |
| not present. | manual. | |
UPS Available |
|
| |
| Refer to 2U Hardwire POD | ||
lamp (green) | UPS input and/or | installation instructions in this | |
not illuminated. | output cord not | manual: | |
| connected to 2U | • Installation on GXT 2U UPS | |
| Hardwire POD. | and | |
|
| • Rack Mount Installation. | |
|
|
| |
2U Hardwire |
| Verify that utility and UPS are | |
POD will not |
| ||
Input power cannot | on, all circuit protectors are | ||
start some / all | |||
support load. | closed, and load is within the | ||
connected | |||
| rating of the power source. | ||
loads. |
| ||
|
| ||
|
|
| |
Utility or UPS | Overcurrent |
| |
circuit | protection on 2U | Recalculate load requirements. | |
protectors trip | Hardwire POD | ||
after resetting. | connected load. |
| |
|
|
|
14