Wiring access doors on each end of the POD allow access to the wiring compartments by opening the top and rear of the POD. Each access door is retained using two Phillips head screws.
The center screw and center panel should not be removed.
Figure 6 Removing wiring access doors
REAR VIEW
CAUTION - RISK OF ELECTRIC SHOCK, SO NOT REMOVE COVER. NO USER SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.
CAUTION - RISK OF ELECTRIC SHOCK, THIS UPS RECEIVES POWER FROM MORE THAN ONE
CAUTION - FOR USE IN A CONTROLLED ENVIRONMENT. REFER TO MANUAL FOR ENVIRONMENTAL CONDITION.
Model No. : |
| |
Desc. | : Micro Pod | C UL US |
Input | : 120VAC 12A | |
| 50/60Hz, 10 | LISTED |
Ouptut | : 120VAC 12A | 91N6 |
| 50/60Hz, 10 | U.P.S. Accessory |
MADE IN TAIWAN |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
| Access |
|
| |||
Remove | Do NOT remove the | ||||||
Door | |||||||
Screws |
|
|
| center screw | |||
|
|
| |||||
|
|
|
|
|
|
|
INSTALLATION OF UPS
1.) MAKE LINE CORD CONNECTION TO UPS SIDE OF POD.
2.) TURN ON UPS BY ITS START INSTRUCTIONS.
3.) ENSURE UPS LAMP IS ILLUMINATED.
Access
Door Remove
Screws
MAINTENANCE OF UPS
1.) ENSURE MAINTENANCE BYPASS LAMP IS ILLUMINATED.
2.) SWITCH TO MAINTENANCE BYPASS POSITION. (LOAD IS NOW UNPROTECTED!)
4.) SWITCH TO UPS POSITION
POWER OUTPUT DISTRIBUTION
3.) TURN UPS OFF AND DISCONNECT UPS CORDS FROM POD.
(LOAD IS NOW PROTECTED BY UPS!)4.) UPS IS NOW AVAILABLE FOR MAINTENANCE
TOP VIEW
Electrical Connections
The wiring compartments provide terminal blocks to connect Line, Neutral, and Ground for both the UTILITY input and LOAD output.
The cable sizes and distribution methods used during installation are subject to local/national electrical codes of practice, and therefore are not detailed here. Table 1 details the standard current ratings.
Properly Grounded (Earthed) Equipment Provides Multiple Benefits
High quality Ground (Earth) connections are required for the equip- ment ground conductors (Protective Earth) (power system earth con- nection) to provide for safe operation of the UPS and connected loads and to reduce electrical noise. Conduit used alone without a grounding conductor wire is not an acceptable connection. Size Ground (Protec- tive Earth) conductors equal in size to circuit conductors.
For wiring information, please refer to Table 1.