RACK MOUNT INSTALLATION

1.Rack mount installation of the 2U POD is possible with the use of the rack mounting brackets (shipped with the POD). See Figure 3.

2.The rack mount brackets allow you to rack mount the POD in a 19" enclosure (23" to 19" rack adapters are available as options from Liebert if you are using 23" Foundation or equivalent cabi- net).

3.The POD can be mounted to face one of four directions depending on your application, and utilizing the rack mount brackets pro- vided.

4.Conduit entry is possible on two sides of the POD. Plan POD ori- entation to allow for wiring. Determine the desired position and direction for the POD, face it in that direction, and then attach the brackets to the POD with the screws provided.

5.Consult your rack/enclosure manufacturer’s recommendations for specific rack mounting hardware that will be required.

6.The holes on the rack mount bracket are notched for easy installa- tion. Tighten the POD securely to the rails and then follow the startup directions for the POD in Installation on GXT 2U UPS.

Figure 3 2U Hardwire POD with rack mounting brackets

LOAD

CAUTION

IF UTILITY LAMP IS ILLUMINATED

MAINTENANCE BYPASS POSITION

 

MAY BE SELECTED

 

SWITCH TO UPS POSITION ONLY

 

WHEN UPS LAMP IS ILLUMINATED

UPS

MAINTENANCE BYPASS

UPS

AVAILABLE

AVAILABLE

 

UPS

UTILITY

 

UTILITY

CONNECT UPS

LINE CORD HERE

5

Page 9
Image 9