![](/images/new-backgrounds/1041280/41280145x1.webp)
Troubleshooting
Table 23 Compressor and refrigeration system troubleshooting
Symptom | Possible Cause | Check or Remedy | |
|
|
| |
| Power off | Check main switch, fuses or CBs and wiring | |
|
|
| |
Compressor will not | Current overload open | Reset manually | |
start | Loose electrical connections | Tighten connections | |
|
|
| |
| Compressor motor burned out | Check and replace compressor if defective. | |
|
|
| |
| No call for cooling | Check monitor status. | |
|
|
| |
Compressor will not | Solenoid valve not energizing | Hold screwdriver over solenoid and check for magnetic field. | |
operate, contactor not | This indicates solenoid is energized. | ||
| |||
pulling in |
|
| |
Low pressure switch not making | Check gas pressure - manually energize low pressure | ||
| |||
| contact | switch. | |
|
|
| |
Compressor will not |
| Reset switch. Refer to other refrigeration troubleshooting | |
operate, contact not | High pressure switch open | ||
suggestions. | |||
pulling in |
| ||
|
| ||
|
|
| |
Compressor contactor |
|
| |
pulled in but | Blown fuse or tripped CB | Check for line voltage after fuses or CBs, and after | |
compressor will not | contactors. | ||
| |||
operate |
|
| |
|
|
| |
Compressor runs for | Low pressure switch not closing | Check for low gas pressure. Compressor is running on | |
three minutes then | Positive Start Kit (air cooled systems only). | ||
| |||
stops; contactor drops |
|
| |
|
| ||
out. Motor operates but | Solenoid not opening | Check magnetic field to see if energized. | |
valve won't open |
|
| |
| Dirty condenser or drycooler fins | Clean coil | |
|
|
| |
| Condenser equipment not | Check operation. | |
| operating | ||
|
| ||
High discharge | High refrigerant charge | Check refrigerant charge. | |
pressure |
|
| |
Hot gas bypass valve adjusted | Adjust properly. | ||
| |||
| improperly | ||
|
| ||
|
|
| |
| Water regulating valve adjusted | Adjust properly. | |
| improperly | ||
|
| ||
| Excessive water now through | Adjust water regulating valve | |
| condenser | ||
|
| ||
| Suction service valve partially | Open the valve. | |
| closed | ||
|
| ||
Low discharge pressure | Leaky compressor suction valves | Pump down, remove the cylinder head, examine valves and | |
valve seats; replace if necessary | |||
|
| ||
| Worn piston rings | Replace compressor. | |
|
|
| |
| Faulty head pressure control |
| |
| valve or condenser fan speed | Replace if defective. | |
| control |
| |
| Insufficient refrigerant in system | Check for leaks, repair, and add refrigerant | |
|
|
| |
| Dirty air filters | Change filters. | |
|
|
| |
| Plugged | Replace filter. | |
|
|
| |
| Improper superheat adjustment | Reset expansion valve for | |
|
|
| |
Low suction pressure | Defective expansion valve | Replace element | |
| sensing element |
| |
| Poor air distribution | Check duct work for closed dampers. Check for underfloor | |
| restrictions at or near the unit. | ||
|
| ||
| Low condensing pressure | Check head pressure control device. | |
|
|
| |
| Slipping belts | Inspect and adjust | |
|
|
|
65