Advanced Microprocessor with Graphics Control Setup
4.14.4Control Outputs
Active control outputs are indicated with LEDs on the lower section of the control board. Each LED is lit if the control output is active (on). Use these LEDs to assist in troubleshooting the system.
Table 12 Control output LEDs
LED | Control Output |
R5 | Heat Rejection |
LLSV1 | Liquid Line Solenoid Valve 1 |
HGBP1 | Hot Gas |
C1 | Compressor 1 |
C2 | Compressor 2 |
RH1 | Reheat Stage 1 or Hot Gas Reheat Solenoid |
RH2 | Reheat Stage 2 |
RH3 | Reheat Stage 3 |
HUM | Humidifier |
HGBP2 | Hot Gas Bypass 2 or Compressor Unloader Valve 2 |
FAN | Main Fan |
HMV | Humidifier |
LLSV2 | Liquid Line Solenoid Valve 2 |
4.15Communications
The control system uses a
Liebert Site Product Device
•SiteScan Centralized Monitoring
•SiteLink BMS Interface
•OpenComms Network Interface
•OpenComms D.O. Interface
•
•ECA2 Communication
Consult the User Manual of the appropriate device for specific installation and operation information.
4.15.1Monitor functions:
1.Temperature/Humidity: Present readings
2.Status: Cooling/Heating and Humidifying/Dehumidifying operating status in percent
3.Present Alarms: Alarms presently active
4.Alarm History: 10 most recent alarms (60 most recent alarms for AG)
5.Run Time Log: Operating hours on major components
6.Daily Log: High and Low Temperature & Humidity
4.15.2View/Change Functions:
1. Setpoints: Temperature Setpoint | High Humidity Alarm |
Temperature Sensitivity | Low Humidity Alarm |
Humidity Setpoint | Cold Start Delay |
Humidity Sensitivity | Humidifier Flush Rate |
High Temperature Alarm | Chilled Water Flush Rate |
Low Temperature Alarm |
|
2.Control Type: Proportional, PID, Intelligent
3.PID Parameters: Proportional, Derivative and Integral Gains
4.On/Off Status
5.Time: View Only
6.Silence Alarm
32