Grounding the Transmitter Case

ENVIRONMENTAL CONSIDERATIONS

Access Requirements

Cover Installation

The transmitter case should always be grounded in accordance with national and local electrical codes. The most effective transmitter case grounding method is direct connection to earth ground with minimal impedance. Methods for grounding the transmitter case include:

Internal Ground Connection: The Internal Ground Connection screw

is inside the FIELD TERMINALS side of the electronics housing. This screw is identified by a ground symbol ( ), and is standard on all Rosemount 3051N transmitters.

External Ground Assembly: This assembly is included as standard with the transient protection terminal block (T1) included with the Rosemount 3051N

NOTE

Grounding the transmitter case using the threaded conduit connection may not provide a sufficient ground. The standard transient protection terminal block (T1) does not provide transient protection unless the transmitter case is properly grounded. Use the above guidelines to ground the transmitter case. Do not run the transient protection ground wire with signal wiring as the ground wire may carry excessive current if a lightning strike occurs.

The following guidelines can help optimize transmitter performance. Mount the transmitter to minimize ambient temperature changes, vibration, mechanical shock, and to avoid external contact with corrosive materials. “Specifications and Reference Data” in Section 5 lists transmitter temperature operating limits.

When choosing an installation location and position, take into account the need for access to the transmitter.

Process Flange Orientation

Mount the process flanges with sufficient clearance for process connections. For safety reasons, place the drain/vent valves so the process fluid is directed away from technicians when the vents are used. In addition, consider the possible need for a testing or calibration input.

Housing Rotation

See “Housing Rotation” in Section 3.

Terminal Side of Electronics Housing

Mount the transmitter so that the terminal side is accessible. A 0.75-inch (19

mm)clearance is required for cover removal. Use a conduit plug on the unused side of the conduit opening.

Circuit Side of Electronics Housing

Provide 0.75 inches (19 mm) clearance for cover removal. Three inches of clearance is required for cover removal if a meter is installed.

Exterior of Electronics Housing

The integral span and zero adjustments are located under the label plate on the top of the transmitter. Allow a minimum of 1.0 inch of clearance above the transmitter if you intend to use the integral zero and span adjustments.

Always install the electronics housing covers metal-to-metal to ensure a proper seal.

3-14

Page 48
Image 48
Emerson Process Management 3051N manual Grounding the Transmitter Case, Environmental Considerations

3051N specifications

The Emerson Process Management 3051N is a state-of-the-art pressure transmitter that exemplifies precision and reliability in process automation. Designed for a wide range of industrial applications, the 3051N is celebrated for its advanced features, innovative technologies, and robust construction, catering to the evolving needs of process industries.

One of the standout features of the 3051N is its exceptional accuracy. With a standard accuracy rating of ±0.075% of span, it ensures precise pressure measurements, critical for maintaining optimal process conditions. This high level of accuracy makes it suitable for applications in industries such as oil and gas, chemicals, and water treatment, where even minor deviations can lead to significant operational issues.

The 3051N employs Smart Pressure Technology, integrating digital communication capabilities with traditional analog systems. This technology allows for seamless interoperability with existing process control systems, providing users with vital data for diagnostics, calibration, and configuration via HART, FOUNDATION fieldbus, or Profibus protocols. These capabilities lead to enhanced process efficiency and reduced downtime due to effective predictive maintenance.

Another notable characteristic of this transmitter is its robust design. The 3051N is built to endure harsh industrial environments, with a rugged housing that is resistant to corrosive and hazardous conditions. Its wide operating temperature range, typically from -40°C to 85°C, coupled with various diaphragm materials, ensures that it can function effectively across diverse applications.

Moreover, the Emerson 3051N incorporates advanced predictive diagnostics, enabling users to monitor the health of the transmitter continuously. This feature alerts operators to potential issues before they escalate, facilitating proactive maintenance strategies that can significantly lower operational costs.

The flexible configuration options offered by the 3051N also enhance its usability. Users can select from a variety of pressure ranges, process connection types, and electrical connections, making it easy to customize the transmitter to fit specific application needs.

In conclusion, the Emerson Process Management 3051N pressure transmitter is a versatile and highly efficient device that integrates advanced technology with robust design and exceptional accuracy. Its ability to adapt to various industrial demands while providing predictive diagnostics makes it a preferred choice for professionals seeking reliability and precision in process management.