EMI T2HA, S2HA manual P-Trapinstallation

Models: S2HA T2HA

1 25
Download 25 pages 18.34 Kb
Page 10
Image 10
P-TRAP INSTALLATION

S2HA & T2HA REFRIGERANT PIPING INSTALLATION SECTION

NOTE: Refrigerant Piping Installation for both the S2HA & T2HA models.

INTERCONNECTING TUBING SPECS

S2HA, T2HA, T3HA, & T4HA models:

Nominal

Maximum

Maximum

Liquid

Suction

Circuit

Line

Line

Length

Lift

Capacity

OD

OD

 

 

9,000

100’

35’

1/4”

1/2”

12,000

100’

35’

1/4”

1/2”

18,000

100’

35’

3/8”

5/8”

24,000

100’

35’

3/8”

3/4”

The system will support refrigerant runs to the inside unit of up to 100' equivalent feet with a 35' rise included. The units are furnished with sweat connections and are equipped with refrigerant valves and Schrader fittings for charging and taking

pressure readings. The following precau- tions should be made:

Be certain no burrs remain on the fittings.

Use only clean refrigeration tubing.

Use tube benders to guard against kinking.

Avoid piping on wet and rainy days and insulate suction line. Be certain that plastic end caps remain in place when inserting through wall openings. Isolate tubing from transmitting vibra- tion to the building or unit and avoid contact with sharp edges. Refrigera- tion valves should be wrapped with a wet rag "heat sink" to protect valves while brazing.

P-TRAP INSTALLATION

A P-trap is recommended when the suc- tion riser is equal to or greater than 20 feet in height.

When the condenser is installed above the evaporator, the P-trap will help the return of oil back to the compressor.

The placement of the P-trap should be at the halfway mark of

the suction riser. For example if the suc- tion riser is 30 feet tall then a P-trap is recom- mended at the 15 foot mark of the suction riser (see Figure #1).

A P-trap may be fabri-

cated using;

(2)street elbows and

(2)regular elbows. A prefabricated trap may be purchased

from a Wholesaler or Distributor how- ever the trap should be shallow as the:

(4)elbow configuration. Each elbow is approximately 2 equivalent feet. One P-trap is equal to approximately 8 equivalent feet.

Figure #1

Multi-zone Heat Pump Condensing Units

10