S2HA & T2HA REFRIGERANT PIPING INSTALLATION SECTION
1. Clean the ends of tubing and insert into
fi ttings.T2HA
Shown
2.Protect the valves by wrapping with a wet rag "heat sink" before brazing.
3.The use of a shield is recommend (one can be made from some scrap metal) to protect the paint.
5.Verify that the correct piston for the sys- tem match is in place, refer to the air handler Installation Instructions.
6.Refer to the indoor air handler Installa- tion Instructions for any specifi c details regarding the connection of tubing. Connect and braze tubing into the in- door air handler.
7.Attach manifold set.
Manifold | Vacuum Pump | Micron Gage |
S2C
Shown
4. Braze tubing into fi ttings.
T2HA
Shown
Manifold Setup For Evacuation
8.Evacuate line to 500 microns or less to ensure all moisture has been removed and there are no leaks.
! WARNING !
It is illegal to discharge refrigerant into the atmosphere. Use proper reclaiming methods & equipment when installing or servicing this unit.
11 | www.enviromaster.com |