T2HA INSTALLATION INSTRUCTIONS
NOTE: For S2HA installation refer to the S2HA Installation Instruction in this manual.
After the T2HA unit is positioned on the concrete slab or platform (refer to the Site Preparation in the front of this manual) the T2HA is ready for installation:
1. Remove the screw on the back panel.
2.Remove panel to expose eletri- cal wiring.
ELECTRICAL WIRING
1.All electrical wiring must be run according to NEC and local codes.
2.Refer to the unit rating plate for voltage, minimum circuit ampacity and over cur- rent protection requirements.
3. Use only HACR type breakers or time delay fuses. Select the wire size accord- ing to the ampacity rating.
Low Volt | High Volt |
|
3.Location of electrical and tubing connec- tions on back of unit (T4C shown).
Common |
|
Suction |
|
Pressure |
|
Access |
|
Point |
|
Vapor |
|
(Suction) |
|
Liquid | High |
| Pressure |
| Reset |
| (18 & 24) |
Remove the four screws on the front panel
4.To access wiring diagram:
a)Remove the four screws on the front panel of the unit and slide the panel down until
the upper edge is free, then remove the panel.
b)The wiring
diagram is |
|
located on |
|
the inside | Wiring |
of the front | Diagram |
panel. |
|
8 | www.enviromaster.com |