GAS SUPPLY

The gas line can be routed either through the floor or wall. The gas line opening should be made at this time. Location of the opening will be determined by the position of floor joists and the valve and union used for servicing.

Gas Supply

Check all local codes for requirements, especially for the size and type of gas supply line required.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Tubing, Type L

 

Inside Diameter

Outside Diameter

 

Nat.

L.P.

Nat.

L.P.

0-10 feet

1/2”

3/8”

1/2”

3/8”

0-3 meters

12.7mm

9.5mm

12.7mm

9.5mm

10-40 feet

1/2”

1/2”

5/8”

1/2”

4-12 meters

12.7mm

12.7mm

15.9mm

12.7mm

40-100 feet

1/2”

1/2”

3/4”

1/2”

13-30 meters

12.7mm

12.7mm

19mm

12.7mm

100-150 feet

3/4”

1/2”

7/8”

3/4”

31-46 meters

19mm

12.7mm

22.2mm

19mm

Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

3 9/16”

GAS INLET

(90mm)

IN BOTTOM

 

OF HEATER

WALL

1 11/16” (43mm)

TO WALL

VIEW FROM TOP OF HEATER

Dimensions Apply to SR-6, SR-10, SR-18

Figure 1

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not ad- equate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.

Figure 2

Method of Installing a Tee Fitting Sediment Trap (Figure 2) The use of the following gas connectors is recommended:

ANS Z21.24 Appliance Connectors of Corrugated Metal Tub- ing and Fittings

ANS Z21.45 Assembled Flexible Appliance Connectors of

Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority having jurisdiction.

Pressure Testing of the Gas Supply System

1.To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.

2.The appliance and its appliance main gas valve must be discon- nected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

3.The appliance must be isolated from the gas supply piping sys- tem by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

Attention! If one of the above procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.

Checking Manifold Pressure

Natural gas will have a manifold pressure of approximately 6.0" w.c. (1.49kPa) at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 7.0" w.c. (1.743kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.615kPa). Propane/LP gas will have a manifold pressure ap- proximately 10.0" w.c. (2.49kPa) at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 11.0" w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0" w.c. (3.237kPa).

A test gage connection is located downstream of the gas appliance pressure regulator for measuring gas pressure. The connection is a 1/8 inch (3mm) N.P.T. plugged tapping.

16942-5-0907

Page 7

Page 7
Image 7
Empire Comfort Systems SR-30 GAS Supply, Gas Supply, Recommended Gas Pipe Diameter, Checking Manifold Pressure

SR-30 specifications

Empire Comfort Systems has established itself as a leading manufacturer of heating appliances, and the SR-30 gas stove is a testament to its dedication to quality and efficiency. This model is designed to seamlessly blend comfort with modern aesthetic appeal, making it an ideal choice for various living spaces.

The Empire SR-30 boasts a compact design that measures 30 inches in height, making it suitable for both small and larger rooms. One of its main features is the ability to provide heat without the need for electricity, thanks to its reliable gas-burning technology. This characteristic ensures that the stove can function during power outages, providing peace of mind and warmth even in unpredictable weather conditions.

Equipped with state-of-the-art burner technology, the SR-30 delivers an impressive heat output, ranging between 20,000 and 30,000 BTUs, capable of effectively warming spaces up to 1,200 square feet. The unit is designed with a built-in thermostat and adjustable flame control, allowing users to customize the heat output according to their comfort preferences.

Safety is a priority with the SR-30, which features a safety shut-off system designed to prevent gas leaks and ensure safe operation. The unit is also equipped with a venting system that promotes effective heat distribution while minimizing draft issues, providing a consistent and cozy warmth throughout the room.

The aesthetic design of the SR-30 is another standout feature. With a range of attractive finishes and an array of customizable options, consumers can choose a style that complements their home décor. The large glass viewing area offers a warm, flickering flame, creating an inviting atmosphere that enhances any space.

In terms of installation, the SR-30 is versatile, as it can be direct-vented or installed using a one-pipe venting system, providing options for various home configurations. Additionally, the unit operates quietly, ensuring it will not disrupt conversations or relaxation.

In conclusion, the Empire Comfort Systems SR-30 gas stove is an excellent choice for homeowners seeking an efficient, reliable, and stylish heating solution. With its powerful heating capabilities, safety features, and elegant design, the SR-30 adds warmth and charm to any living environment.