Unpacking the DC Power Supply
Warning: To reduce the risk of electric shock or energy hazards: 1. Connect to a reliably grounded 48V source.
2.The branch circuit over current protection must be rated at a maximum 50A for the device.
3.Use only 10mm² or 6 AWG 75C solid copper wires on the device.
4.A readily accessible disconnect device that is suitably approved and rated shall be incorporated in the field wiring.
5.To be installed in a restricted access area in accordance with the NEC or authority having jurisdiction.
Advertencia: Para reducir el riesgo de choque electrico:
1.Conectar a una fuente aterrizada de 48V.
2.The branch circuit over current protection must be rated at a maximum 50A for the device.
3.Utilizar unicamente cables de cobre solidos de tipo 75C 10mm² or 6 AWG en el dispositivo.
4.A readily accessible disconnect device that is suitably approved and rated shall be incorporated in the field wiring.
5.Ser instalado en una area de acceso restrictivo, de acuerdo con el NEC o con otra autoridad.
Warnhinweis: Reduzieren sie das Risiko von Stromschlägen oder allgemeinen elektrischen Gefahren:
1.Verbinden Sie das Gerät mit einer zuverlässig geerdeten 48 V Stromquelle.
2.Die maximale Absicherung des Stromkreises für dieses Gerät beträgt 50A.
3.Benutzen Sie zum Anschluß des Gerätes ausschließlich Kabel mit soliden Kupferadern des Querschnitts 10mm² (6 AWG) 75C.
4.Das Stromnetz am Installationsort sollte mit einem frei zugänglichen Spannungs- Unterbrecher
5.Die Installation sollte in zugangskontrollierten Räumen erfolgen, entsprechend den Vorschriften der NEC bzw. der örtlich zuständigen Behörden.
Unpacking the DC Power Supply
To unpack the DC power supply:
1.Open the box and remove the packing material protecting the DC power supply.
2.Verify the contents of the carton as listed in Table 1‐4.
Matrix X Router DC Power Supply Installation Guide